Basic type

Three-phase 400V series

(0.4 to 55kW) HD (High Duty) spec for heavy load
(75 to 630kW) HD (High Duty) spec for heavy load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

(5.5 to 55kW) LD (Low Duty) spec for light load
(75 to 630kW) LD (Low Duty) spec for light load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

Three-phase 460V series

LD (Low Duty)-mode inverters for light load

*1

US 4P-standard induction motor

*2

Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.

*3

Output voltage cannot exceed the power supply voltage.

*4

Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V)) × 67 (IEC 61800- 3))
If this value is 2 to 3%, use an optional AC reactor (ACR).

*5

Required when a DC reactor (DCR) is used.

*6

Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)

*7

The FRN100G1S-4U or higher type comes with a DC reactor (DCR).

*1

US 4P-standard induction motor

*2

Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.

*3

Output voltage cannot exceed the power supply voltage.

*4

Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V)) × 67 (IEC 61800- 3))
If this value is 2 to 3%, use an optional AC reactor (ACR).

*5

Required when a DC reactor (DCR) is used.

*6

Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)

*7

The FRN100G1S-4U or higher type comes with a DC reactor (DCR).

MD (Medium Duty)-mode inverters for medium load

*1

US 4P-standard induction motor

*2

Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.

*3

Output voltage cannot exceed the power supply voltage.

*4

Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V)) × 67 (IEC 61800- 3))
If this value is 2 to 3%, use an optional AC reactor (ACR).

*5

Required when a DC reactor (DCR) is used.

*6

Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)

*7

The FRN100G1S-4U or higher type comes with a DC reactor (DCR).

HD (High Duty)-mode inverters for heavy load

*1

US 4P-standard induction motor

*2

Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.

*3

Output voltage cannot exceed the power supply voltage.

*4

Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V)) × 67 (IEC 61800- 3))
If this value is 2 to 3%, use an optional AC reactor (ACR).

*5

Required when a DC reactor (DCR) is used.

*6

Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)

*7

The FRN100G1S-4U or higher type comes with a DC reactor (DCR).

*1

US 4P-standard induction motor

*2

Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.

*3

Output voltage cannot exceed the power supply voltage.

*4

Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V)) × 67 (IEC 61800- 3))
If this value is 2 to 3%, use an optional AC reactor (ACR).

*5

Required when a DC reactor (DCR) is used.

*6

Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)

*7

The FRN100G1S-4U or higher type comes with a DC reactor (DCR).

Three-phase 400V series

(0.4 to 55kW) HD (High Duty) spec for heavy load
(75 to 630kW) HD (High Duty) spec for heavy load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

(5.5 to 55kW) LD (Low Duty) spec for light load
(75 to 630kW) LD (Low Duty) spec for light load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

Three-phase 400V series

(0.4 to 55kW) HD (High Duty) spec for heavy load
(75 to 630kW) HD (High Duty) spec for heavy load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

(5.5 to 55kW) LD (Low Duty) spec for light load
(75 to 630kW) LD (Low Duty) spec for light load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

Three-phase 400V series

(0.4 to 55kW) HD (High Duty) spec for heavy load
(75 to 630kW) HD (High Duty) spec for heavy load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

(5.5 to 55kW) LD (Low Duty) spec for light load
(75 to 630kW) LD (Low Duty) spec for light load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

Three-phase 400V series

(0.4 to 55kW) HD (High Duty) spec for heavy load
(75 to 630kW) HD (High Duty) spec for heavy load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.

(5.5 to 55kW) LD (Low Duty) spec for light load
(75 to 630kW) LD (Low Duty) spec for light load

*1

Fuji's 4-pole standard motor

*2

Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.

*3

Output voltage cannot exceed the power supply voltage.

*5

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)

*6

Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.

*7

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*8

Obtained when a DC reactor (DCR) is used.

*9

Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)

*10

A DC reactor (DCR) is an option. However, Inverters with a capacity of 75kW(HD spec) or above, 55kW(LD spec) or above, require a DCR to be connected. Be sure to connect it to those inverters.

*11

FRN160,200,220,355 and 400G1□-4A can not apply to the C22.2 No.14.