FRENIC-MEGA (G2)
Standard Specifications | Three-phase 200V

Basic Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC Filter Built‑In Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Zero‑Phase Reactor Built‑In Type(Three-phase 200V)

High carrier frequency Normal Duty

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

DCR Built‑In Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note9

This is the value at the rated output when the voltage unbalance of the power supply is 0%

Basic Type(Three-phase 200V)

Note1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note3

It is not possible to output a voltage higher than the power supply voltage.

Note5

Interphase unbalance ratio [%] = (Max. voltage [V] - min. voltage [V]/Three-phase average voltage [V] x 67 (see IEC/EN 61800-3).
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).

Note6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note9

When applying a motor of 75kW or more, be sure to use a DC reactor (option).

Basic Type(Three-phase 230V)

Note1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note3

It is not possible to output a voltage higher than the power supply voltage.

Note5

Interphase unbalance ratio [%] = (Max. voltage [V] - min. voltage [V]/Three-phase average voltage [V] x 67 (see IEC/EN 61800-3).
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).

Note6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note9

When applying a motor of 75kW or more, be sure to use a DC reactor.

Note10

For G2△, Type 0003 to 0215 indicate G2S, and type 0288 to 0432 indicate G2W.

This type is not available in this region.
If you need more information for this products, please contact us through the inquiry form.

Basic Type(Three-phase 200V)

Note1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note3

It is not possible to output a voltage higher than the power supply voltage.

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note9

When applying a motor of 75kW or more, be sure to use a DC reactor (option).

Basic Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC Filter Built‑In Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Zero‑Phase Reactor Built‑In Type(Three-phase 200V)

High carrier frequency Normal Duty

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

DCR Built‑In Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note9

This is the value at the rated output when the voltage unbalance of the power supply is 0%

Basic Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC Filter Built‑In Type(Three-phase 200V)

Note1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note3

Output voltage cannot exceed the power supply voltage.

Note4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note6

Required when a DC reactor (DCR) is used.

Note7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Contact and Support

Online inquiries
Contact Us