FRENIC-MEGA (G2)
Standard Specifications | Three-phase 200V

Basic type(Three-phase 200V)

Note 1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note 2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note 3

It is not possible to output a voltage higher than the power supply voltage.

Note 5

Interphase unbalance ratio [%] = (Max. voltage [V] - min. voltage [V]/Three-phase average voltage [V] x 67 (see IEC/EN 61800-3).
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).

Note 6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note 7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note 8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 9

When applying a motor of 75kW or more, be sure to use a DC reactor (option).

Basic type(Three-phase 200V)

Note 1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note 2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note 3

It is not possible to output a voltage higher than the power supply voltage.

Note 5

Interphase unbalance ratio [%] = (Max. voltage [V] - min. voltage [V]/Three-phase average voltage [V] x 67 (see IEC/EN 61800-3).
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).

Note 6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note 7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note 8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 9

When applying a motor of 75kW or more, be sure to use a DC reactor (option).

Basic type(Three-phase 200V)

Note 1

Standard applicable motor indicates Fuji Electric 4-pole standard motors. Select a motor not only based on inverter output (kW), but also so that the output rated current is greater than the motor rated current.

Note 2

The rated capacity indicates 220 V for the 200 V series, and 440 V for the 400 V series.

Note 3

It is not possible to output a voltage higher than the power supply voltage.

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

This indicates the estimated value if the power supply capacity is 500 kVA (10 times inverter capacity if inverter capacity exceeds 50 kVA), and the motor is connected to a power supply of %X = 5%.

Note 7

This indicates the capacity when the motor is equipped with a DC reactor (DCR).

Note 8

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 9

When applying a motor of 75kW or more, be sure to use a DC reactor (option).

Basic type(Three-phase 200V)(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC filter built-in type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Zero-phase built-in reactor type(Three-phase 200V)

High carrier frequency Normal Duty

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

DCR built-in type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 9

This is the value at the rated output when the voltage unbalance of the power supply is 0%

Basic type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC filter built-in type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Basic type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

EMC filter built-in type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

Zero-phase built-in reactor type(Three-phase 200V)

High carrier frequency Normal Duty

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 8

When using a motor with a rating of 75 kW or more, be sure to use a DC reactor (option).

DCR built-in type(Three-phase 200V)

Note 1

Fuji's 4-pole standard motor When selecting an inverter, in addition to considering the kWs of the inverter, make sure that the output current rating is larger than the motor current rating.

Note 2

Rated capacity is calculated by assuming the rated output voltage as 220 V for 200 V series and 440 V for 400 V series.

Note 3

Output voltage cannot exceed the power supply voltage.

Note 4

Voltage unbalance(%) =Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) ×67 (IEC 61800-3) If this value is 2 to 3%, use an optional AC reactor (ACR).

Note 5

These values are calculated on assumption that the inverter is connected to a power supply with a capacity of 500 kVA (or 10 times the inverter capacity when the inverter capacity exceeds 50 kVA) and %X is 5%.

Note 6

Required when a DC reactor (DCR) is used.

Note 7

This is the average braking torque when performing individual operation. (This will vary based on the motor efficiency.)

Note 9

This is the value at the rated output when the voltage unbalance of the power supply is 0%

Contact Us