Specifications

Unit Type
LD specifications for light overload (Unit Type)
Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□ VG1S-□ J: 45kW or below: provided as option, 55kW or above: provided as standard.
(Specify LD specification when placing your order.)

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "UnitType, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□VG1S-□E : All capacities are provided as option.

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□VG1S-□E : All capacities are provided as option.

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□VG1S-□C : All capacities are provided as option.

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□VG1S-□E : All capacities are provided as option.

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□ VG1S-□ J: 45kW or below: provided as option, 55kW or above: provided as standard.
(Specify LD specification when placing your order.)

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)

Three-phase 200V series
Three-phase 400V series

Note 1

The above specifications are for Function Code F80=1 (LD specification).
If using with an LD specification of 55kW or higher, specify LD specification when placing your order.
With the type FRN□ VG1S-□ J, a DC reactor with nominal applied motor capacity is provided as standard.

Note 2

When using a DC reactor, refer to the following.
・Type FRN□ VG1S-□ J: 45kW or below: provided as option, 55kW or above: provided as standard.
(Specify LD specification when placing your order.)

*1

The rated output voltage is 220V for 200V series and 440V for 400V series.

*2

When the converted inverter output frequency is less than 10Hz, the inverter may trip earlier in some ambient temperature conditions if the motor is overloaded.

*3

200V series: Make an individual order for 220 to 230V/50Hz.
400V series: The inverters with the power supply of 380 to 398V/50Hz and 380 to 430V/60Hz must be switched using a connector inside the inverter.
The output of the inverter with 380V may drop depending on situations. For details, refer to Chapter 10 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A- -0019.

*4

The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function.(Generally not used.)

*5

Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V]) / (Three-phase average voltage [V]) × 67
Use an AC reactor if the voltage unbalance exceeds 2%.

*6

The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.

*7

The values shown apply when a DC reactor is used.
If using a generator for the power source, it may burn out with high-frequency current from the inverter. Use a generator with 3 to 4 times the specified power supply capacity.
(When DC reactor not connected: approx. 4 times specified power supply capacity, when DC reactor connected: approx. 3 times specified power supply capacity)

*8

The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
If the carrier frequency auto reduction selection (H104: digit 100) is cancelled, the unit continuous rated current will drop depending on the carrier frequency setting, and therefore caution is advised.
(For details, refer to Chapter 2 in the FRENIC-VG User Manual "Unit Type, Function Code Edition" 24A7-□-0019.)