FRENIC-Lift (LM3)
Specifications | 3ph 200V

3ph 200V

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.

Note 1

Standard applicable motors are for Fuji Electric's 4-pole standard motors.

Note 2

The rated capacity is for 200V series: 220V rating.

Note 3

A voltage higher than the power supply voltage cannot be output.

Note 4

Indicates when the ambient temp. is 50°C 10kHz, the carrier frequency.
Select the inverter capacity so that the mean square current in operation is 80% or less of the inverter rated current.

Note 5

This is the estimated value when the power supply capacity is 500 kVA and connected to the power supply of %X=5%.

Note 6

Indicates the type with a DC reactor (DCR).

Note 7

Phase-to-phase imbalance ratio [%] =
(Refer to max. voltage [V]-min. voltage [V])/3-phase averaging voltage [V] × 67(IEC/EN 61800-3)
Use an AC reactor (ACR: optional) when using with an unbalance ratio of 2 to 3%.

Note 8

In UPS operation or battery operation, only the braking operation can be used. Cannot be used in load operation.
Connect UPS or battery power supply to L1/R,L3/T.

Note 9

Braking time and braking duty ratio (%ED) are defined by cycling operation at the rated regenerative power shown
in the diagram below.

Note 10

he allowable error of the minimum connectable resistance value is ±5%.