Standard specifications

Three-phase 400V series (0.75 to 55kW)

Item Specifications
Type
(FRNF1S-4J)
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Nominal applied motor (kW) *1 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Output ratings Rated capacity (kVA) *2 1.9 2.8 4.1 6.8 9.5 12 17 22 28 33 44 54 64 77
Rated voltage (V) *3 Three-phase, 380 to 480V (with AVR function)
Rated current (A) *4 2.5 3.7 5.5 9 12.5 16.5 23 30 37 44 59 72 85 105
Overload capability 120% of rated current for 1min
Rated frequency 50, 60Hz
Input ratings Phases,
voltage,
frequency
Main power supply Three-phase, 380 to 480V, 50/60Hz Three-phase, 380 to 440V/50Hz
Three-phase, 380 to 480V/60Hz
Auxiliary control
power input
Single-phase, 380 to 480V, 50/60Hz Single-phase, 380 to 440V/50Hz
Single-phase, 380 to 480V/60Hz
Auxiliary fan power input *9 - *10
Voltage/frequency allowance Voltage: +10 to -15% (Voltage unbalance: 2% or less) *8, Frequency: +5 to -5%
Rated current (A) *5 (with DCR) 1.6 3 4.5 7.5 10.6 14.4 21.1 28.8 35.5 42.2 57.0 68.5 83.2 102
(without DCR) 3.1 5.9 8.2 13.0 17.3 23.2 33.0 43.8 52.3 60.6 77.9 94.3 114 140
Required power supply capacity (kVA) *6 1.2 2.2 3.1 5.3 7.4 10 15 20 25 30 40 48 58 71
Braking Torque (%) *7
20
10 to 15
DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
DC reactor (DCR) Option
Applicable safety standards UL508C, C22.2 No.14, EN50178:1997 (Applying)
Enclosure (IEC60529) UL508C, C22.2 No.14, EN50178:1997 (Applying)
IP20, UL open type
IP00, UL open type
Cooling method Natural cooling Fan cooling
Mass (kg) 3.1 3.2 3.3 3.4 5.8 6.0 6.9 3.4 9.4 9.9 11.5 23 24 33

Page Top

Three-phase 400V series (75 to 560kW)

Item Specifications
Type
(FRNF1S-4J)
75 90 110 132 160 200 220 280 315 355 400 450 500 560
Nominal applied motor (kW) 75 90 110 132 160 200 220 280 315 355 400 450 500 560
Output ratings
Rated capacity (kVA) *2105 128 154 182 221 274 316 396 445 495 584 640 731 792
Rated voltage (V) *3 Three-phase, 380 to 480V (with AVR function)
Rated current (A) *4 139 168 203 240 290 360 415 520 585 650 740 840 960 1040
Overload capability 120% of rated current for 1min
Rated frequency 50, 60Hz
Input ratings
Phases,
voltage,
frequency
Main power supply Three-phase, 380 to 440V, 50Hz or
Three-phase, 380 to 480V, 60Hz
Auxiliary control power input Single-phase, 380 to 480V, 50/60Hz
Auxiliary fan
power input *9
Single-phase, 380 to 440V/50Hz
Single-phase, 380 to 480V/60Hz
Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance: 2% or less) *8, Frequency: +5 to -5%
Rated current (A) *5 (with DCR) 138 164 201 238 286 357 390 500 559 628 705 789 881 990
(without DCR) - - - - - - - - - - - - -  
Required power supply capacity (kVA) *6 96 114 140 165 199 248 271 347 388 435 489 547 611 686
Braking
Torque (%) *7
10 to 15
DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
DC reactor (DCR) Option
Applicable safety standards UL508C, C22.2 No.14, EN50178:1997 (Applying)
Enclosure (IEC60529) IP20, UL open type
Cooling method Fan cooling
Mass (kg) 34 42 45 63 67 96 98 162 165 282 286 355 360 360
*1Fuji 4-pole standard motor
*2Rated capacity is calculated by assuming the output rated voltage as 440V for three-phase 400 V series.
*3Output voltage cannot exceed the power supply voltage.
*4An excessively low setting of the carrier frequency may result in the higher motor temperature or tripping of the inverter by its overcurrent limiter setting. Lower the continuous load or maximum load instead. (When setting the carrier frequency (F26) to 1kHz, reduce the load to 80% of its rating.)
*5Trial calculation done on assumption that the power capacity is 500kVA (or 10 times the inverter capacity if the inverter capacity is larger than 50kVA) and the inverter is connected to the power supply of %X=5%.
*6Obtained when a DC reactor (DCR) is used.
*7Average braking torque (Varies with the efficiency of the motor.)
*8Voltage unbalance (%) = ( MAX. voltage(V) - Min. voltage(V) ) / ( Therr-phase average voltage(V) ) x 67 (IEC61800-3)
If this value is 2 to 3%, use an AC reactor (ACR option).
*9 Use [R1, T1] terminals for driving AC cooling fans of an inverter powered by the DC link bus, such as by a high power factor PWM converter. (In ordinary operation, the terminals are not used.)
*10 Single-phase, 380 to 440V/50Hz or Single-phase, 380 to 480V/60Hz