Standard specifications
Three-phase 400V series (0.75 to 55kW)
Item | Specifications | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Type (FRNF1S-4J) |
0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | ||
Nominal applied motor (kW) *1 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | ||
Rated capacity (kVA) *2 | 1.9 | 2.8 | 4.1 | 6.8 | 9.5 | 12 | 17 | 22 | 28 | 33 | 44 | 54 | 64 | 77 | ||
Rated voltage (V) *3 | Three-phase, 380 to 480V (with AVR function) | |||||||||||||||
Rated current (A) *4 | 2.5 | 3.7 | 5.5 | 9 | 12.5 | 16.5 | 23 | 30 | 37 | 44 | 59 | 72 | 85 | 105 | ||
Overload capability | 120% of rated current for 1min | |||||||||||||||
Rated frequency | 50, 60Hz | |||||||||||||||
Phases, voltage, frequency |
Main power supply | Three-phase, 380 to 480V, 50/60Hz | Three-phase, 380 to 440V/50Hz | |||||||||||||
Three-phase, 380 to 480V/60Hz | ||||||||||||||||
Auxiliary control power input |
Single-phase, 380 to 480V, 50/60Hz | Single-phase, 380 to 440V/50Hz | ||||||||||||||
Single-phase, 380 to 480V/60Hz | ||||||||||||||||
Auxiliary fan power input *9 | - | *10 | ||||||||||||||
Voltage/frequency allowance | Voltage: +10 to -15% (Voltage unbalance: 2% or less) *8, Frequency: +5 to -5% | |||||||||||||||
Rated current (A) *5 | (with DCR) | 1.6 | 3 | 4.5 | 7.5 | 10.6 | 14.4 | 21.1 | 28.8 | 35.5 | 42.2 | 57.0 | 68.5 | 83.2 | 102 | |
(without DCR) | 3.1 | 5.9 | 8.2 | 13.0 | 17.3 | 23.2 | 33.0 | 43.8 | 52.3 | 60.6 | 77.9 | 94.3 | 114 | 140 | ||
Required power supply capacity (kVA) *6 | 1.2 | 2.2 | 3.1 | 5.3 | 7.4 | 10 | 15 | 20 | 25 | 30 | 40 | 48 | 58 | 71 | ||
Torque (%) *7 | 20 |
10 to 15 |
||||||||||||||
DC injection braking | Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% | |||||||||||||||
DC reactor (DCR) | Option | |||||||||||||||
Applicable safety standards | UL508C, C22.2 No.14, EN50178:1997 (Applying) | |||||||||||||||
Enclosure (IEC60529) | UL508C, C22.2 No.14, EN50178:1997 (Applying) IP20, UL open type |
IP00, UL open type | ||||||||||||||
Cooling method | Natural cooling | Fan cooling | ||||||||||||||
Mass (kg) | 3.1 | 3.2 | 3.3 | 3.4 | 5.8 | 6.0 | 6.9 | 3.4 | 9.4 | 9.9 | 11.5 | 23 | 24 | 33 |
Three-phase 400V series (75 to 560kW)
Item | Specifications | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Type (FRNF1S-4J) |
75 | 90 | 110 | 132 | 160 | 200 | 220 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | ||
Nominal applied motor (kW) | 75 | 90 | 110 | 132 | 160 | 200 | 220 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | ||
Rated capacity (kVA) *2 | 105 | 128 | 154 | 182 | 221 | 274 | 316 | 396 | 445 | 495 | 584 | 640 | 731 | 792 | ||
Rated voltage (V) *3 | Three-phase, 380 to 480V (with AVR function) | |||||||||||||||
Rated current (A) *4 | 139 | 168 | 203 | 240 | 290 | 360 | 415 | 520 | 585 | 650 | 740 | 840 | 960 | 1040 | ||
Overload capability | 120% of rated current for 1min | |||||||||||||||
Rated frequency | 50, 60Hz | |||||||||||||||
Phases, voltage, frequency |
Main power supply | Three-phase, 380 to 440V, 50Hz or Three-phase, 380 to 480V, 60Hz |
||||||||||||||
Auxiliary control power input | Single-phase, 380 to 480V, 50/60Hz | |||||||||||||||
Auxiliary fan power input *9 |
Single-phase, 380 to 440V/50Hz Single-phase, 380 to 480V/60Hz |
|||||||||||||||
Voltage/frequency variations | Voltage: +10 to -15% (Voltage unbalance: 2% or less) *8, Frequency: +5 to -5% | |||||||||||||||
Rated current (A) *5 | (with DCR) | 138 | 164 | 201 | 238 | 286 | 357 | 390 | 500 | 559 | 628 | 705 | 789 | 881 | 990 | |
(without DCR) | - | - | - | - | - | - | - | - | - | - | - | - | - | |||
Required power supply capacity (kVA) *6 | 96 | 114 | 140 | 165 | 199 | 248 | 271 | 347 | 388 | 435 | 489 | 547 | 611 | 686 | ||
Torque (%) *7 | 10 to 15 |
|||||||||||||||
DC injection braking | Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% | |||||||||||||||
DC reactor (DCR) | Option | |||||||||||||||
Applicable safety standards | UL508C, C22.2 No.14, EN50178:1997 (Applying) | |||||||||||||||
Enclosure (IEC60529) | IP20, UL open type | |||||||||||||||
Cooling method | Fan cooling | |||||||||||||||
Mass (kg) | 34 | 42 | 45 | 63 | 67 | 96 | 98 | 162 | 165 | 282 | 286 | 355 | 360 | 360 |
*1 | Fuji 4-pole standard motor |
*2 | Rated capacity is calculated by assuming the output rated voltage as 440V for three-phase 400 V series. |
*3 | Output voltage cannot exceed the power supply voltage. |
*4 | An excessively low setting of the carrier frequency may result in the higher motor temperature or tripping of the inverter by its overcurrent limiter setting. Lower the continuous load or maximum load instead. (When setting the carrier frequency (F26) to 1kHz, reduce the load to 80% of its rating.) |
*5 | Trial calculation done on assumption that the power capacity is 500kVA (or 10 times the inverter capacity if the inverter capacity is larger than 50kVA) and the inverter is connected to the power supply of %X=5%. |
*6 | Obtained when a DC reactor (DCR) is used. |
*7 | Average braking torque (Varies with the efficiency of the motor.) |
*8 | Voltage unbalance (%) = ( MAX. voltage(V) - Min. voltage(V) ) / ( Therr-phase average voltage(V) ) x 67 (IEC61800-3) If this value is 2 to 3%, use an AC reactor (ACR option). |
*9 | Use [R1, T1] terminals for driving AC cooling fans of an inverter powered by the DC link bus, such as by a high power factor PWM converter. (In ordinary operation, the terminals are not used.) |
*10 | Single-phase, 380 to 440V/50Hz or Single-phase, 380 to 480V/60Hz |