Home > Products & Solutions > AC Drives (LV) > FRENIC-Eco > Product Information - Specifications > Built-in DC reactor series Three-phase 200V series

Specifications Built-in DC reactor series

Built-in DC reactor series

Three-phase 200V series

Item Specifications
Type
(FRNF1H-2J)
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Applicable motor rating [kW] *1 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Output ratings Rated capacity [kVA] *2 1.6 2.6 4,0 8,3 8.3 11 16 21 25 30 40 49 59 75 102
Voltage [V] *3 Three-phase 200 to 240V (with AVR function)
Rated current [A] *4,*9 4.2 7.0 10.6 16.7 23.8
(22.5)
31.8
(29)
45
(42)
58
(55)
73
(68)
85
(80)
114
(107)
140
(130)
170
(156)
211
(198)
276
(270)
Overload capability 120% of rated current for 1min
Rated frequency [Hz] 50, 60Hz
Input ratings Phases,
voltage,
frequency
Main power supply Three-phase, 200 to 240V, 50/60Hz Three-phase, 200 to 220V/50Hz
Three-phase, 200 to 230V/60Hz
Auxiliary control power input Single-phase, 200 to 240V, 50/60Hz Single-phase, 200 to 220V/50Hz
Single-phase, 200 to 230V/60Hz
Auxiliary fan power input *8 - Single-phase, 200 to 220V/50Hz
Single-phase, 200 to 230V/60Hz
Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance: 2% or less *7), Frequency: +5 to -5%
Rated input current [A] *5 3.2 6.1 8.9 15.0 21.1 28.8 42.2 57.6 71.0 84.4 114 138 167 203 282
Required power supply capacity [kVA] 1.2 2.2 3.1 5.3 7.4 10 15 20 25 30 40 48 58 71 98
Braking Braking torque [%] *6
20
10-15
DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60%
Reactor unit DC REACTOR Provided (If load of 100% is used (rated output) used, power supply ratio is above 86%.)
Zero-phase reactor Provided (for radio noise reduction) Not provided
Capacitive filter Provided (removable) Not provided
Applicable safety standards UL508C, C22.2No.14, EN50178: 1997 (Approval pending)
Enclosure (IEC60529) IP20, UL open type IP20, UL type1 (NEMA1)
Cooling method Natural cooling Fan cooling
Weight / Mass [kg] 5.9 6.2 6.6 6.7 6.9 12.7 13.6 15.3 18.7 19.5 23 39 52 55 63
*1Fuji 4-pole standard motor
*2Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.
*3Output voltage cannot exceed the power supply voltage.
*4When the carrier frequency is low, the temperature of the motor may increases rapidly or the inverter protection (current limit) may activate.
When setting the carrier frequency to 1kHz or less, reduce the load to 80% of its rated value.
*5The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
*6Average braking torque without optional braking resistor (Varies with the efficiency of the motor.)
*7Voltage unbalance (%) = ( MAX. voltage(V) - Min. voltage(V) ) / ( Therr-phase average voltage(V) ) x 67 (compliant with IEC61800-3)
If this value is 2 to 3%, use an AC REACTOR (ACR option).
*8 It is used as an AC fan power supply input for applications combined with a high power-factor PWM converter with power regeneration function or the like (not used during normal operation).
*9 Use the inverter at the current given in ( ) or below when the carrier frequency setting is higher than 3kHz or the ambient temperature is 40°C or higher.