Item |
Specifications |
Type (FRN□□□G1E-4□) |
0.4 |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
Nominal applied motor [kW] (*1) |
0.4 |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
Output ratings |
Rated capacity [kVA] (*2)
|
1.1 |
1.9 |
2.8 |
4.1 |
6.8 |
10 |
14 |
18 |
24 |
29 |
34 |
45 |
57 |
69 |
85 |
Rated voltage [V] (*3) |
Three-phase 380 to 480V (with AVR) |
Rated Current [A] |
1.5 |
2.5 |
4 |
5.5 |
9 |
13.5 |
18.5 |
24.5 |
32 |
39 |
45 |
60 |
75 |
91 |
112 |
Overload capability
|
150% for 1min, 200% for 3.0s |
Rated frequency [Hz] |
50, 60Hz |
Input ratings |
Main circuit power
Phases, voltage, frequency
|
Three-phase 380 to 480V, 50/60Hz |
Auxiliary control power input
Phases, voltage, frequency |
- |
Single-phase 380 to 480V, 50/60Hz |
Auxiliary power input for fan
Phases, voltage, frequency (*5)
|
- |
Voltage, frequency variations |
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5% |
Rated current [A] (*7) |
with DCR |
0.85 |
1.6 |
3.0 |
4.5 |
7.5 |
10.6 |
14.4 |
21.1 |
28.8 |
35.5 |
42.2 |
57.0 |
68.5 |
83.2 |
102 |
without DCR |
1.7
|
3.1 |
5.9 |
8.2 |
13.0 |
17.3 |
23.2 |
33 |
43.8 |
52.3 |
80.6 |
77.9 |
94.3 |
114 |
140 |
Required power supply capacity [kVA] (*8)
|
with DCR |
0.6
|
1.2 |
2.1 |
3.2 |
5.2 |
7.4 |
10 |
15 |
20 |
25 |
30 |
40 |
48 |
58 |
71 |
Braking |
Torque [%] (*9)
|
150% |
100% |
20%
|
10 to 15% |
Braking transistor
|
Built-in |
- |
Min. ohmic value [Ω] Torque [%]
|
200
180% |
180
180% |
96
180% |
64
180%
|
48
180% |
32
180%
|
24
180% |
16
180% |
- |
Built-in braking resistance |
720Ω
|
470Ω |
160Ω |
80Ω |
- |
Braking time[s] |
5s |
- |
%ED |
5
|
3 |
5 |
3 |
2 |
3 |
2 |
- |
DC injection braking |
Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 100% |
EMC filter
|
EMC standard compliance: Category C3 is only emission and 2nd Env. is immunity. (EN61800-3:2004)
|
DC reactor (DCR) (*10) |
Optional |
Applicable safety standards
|
UL508C, C22.2No.14 (pending), EN61800-5-1:2003 |
Enclosure (IEC60529)
|
IP20 (IEC60529) closed type, UL open type (UL 50) |
IP00 open type, UL open type |
Cooling method
|
Natural cooling |
Fan cooling |
Weight/Mass [kg] |
2.0
|
2.2 |
3.0 |
3.2 |
3.4 |
7.1 |
7.6 |
7.6 |
10.7 |
10.7 |
11.2 |
26 |
26 |
32 |
36 |
|
|
|
|
(*1) |
Fuji's 4-pole standard motor 。
|
(*2) |
Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series. |
(*3) |
Output voltage cannot exceed the power supply voltage. |
(*5) |
The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)
|
(*6) |
Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.
|
(*7) |
The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
|
(*8) |
Obtained when a DC reactor (DCR) is used.
|
(*9) |
Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)
|
(*10) |
The 55kW DC reactor (DCR) is optional with HD spec, and is provided as a standard accessory with LD spec. |
|
|
|