Standard Specifications EMC type

Three-phase 400V series

(0.4 to 55kW)  HD (High Duty) spec for heavy load
Item
Specifications
Type (FRN□□□G1E-4□) 0.4 0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Nominal applied motor [kW] (*1)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Output ratings Rated capacity [kVA] (*2)
1.1
1.9
2.8
4.1
6.8
10
14
18
24
29
34
45
57
69
85
Rated voltage [V] (*3)
Three-phase 380 to 480V (with AVR)
Rated Current [A]
1.5
2.5
4
5.5
9
13.5
18.5
24.5
32
39
45
60
75
91
112
Overload capability
150% for 1min, 200% for 3.0s
Rated frequency [Hz]
50, 60Hz
Input ratings Main circuit power
Phases, voltage, frequency
Three-phase 380 to 480V, 50/60Hz
Auxiliary control power input
Phases, voltage, frequency
-
Single-phase 380 to 480V, 50/60Hz
Auxiliary power input for fan
Phases, voltage, frequency (*5)
-
Voltage, frequency variations
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5%
Rated current [A] (*7) with DCR 0.85 1.6 3.0 4.5 7.5 10.6
14.4
21.1
28.8
35.5 42.2 57.0 68.5 83.2 102
without DCR 1.7
3.1 5.9 8.2 13.0 17.3 23.2
33
43.8 52.3 80.6 77.9 94.3 114
140
Required power supply capacity [kVA] (*8)
with DCR 0.6
1.2 2.1 3.2 5.2 7.4
10
15
20
25
30
40
48
58
71
Braking Torque [%] (*9)
150%
100%
20%
10 to 15%
Braking transistor
Built-in
-
Min. ohmic value [Ω]
Torque [%]
200
180%
180 180% 96 180% 64 180%
48 180% 32 180%
24 180% 16
180%
-
Built-in braking resistance 720Ω
470Ω 160Ω 80Ω
-
Braking time[s] 5s -
%ED
5
3 5 3 2 3
2
-
DC injection braking
Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 100%
EMC filter
EMC standard compliance: Category C3 is only emission and 2nd Env. is immunity. (EN61800-3:2004)
DC reactor (DCR) (*10) Optional
Applicable safety standards
UL508C, C22.2No.14 (pending), EN61800-5-1:2003
Enclosure (IEC60529)
IP20 (IEC60529) closed type, UL open type (UL 50)
IP00 open type, UL open type
Cooling method
Natural cooling
Fan cooling
Weight/Mass [kg] 2.0
2.2 3.0 3.2 3.4
7.1
7.6
7.6
10.7
10.7
11.2
26
26
32
36
(*1)
Fuji's 4-pole standard motor 。
(*2)
Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.
(*3)
Output voltage cannot exceed the power supply voltage.
(*5)
The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)
(*6)
Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.
(*7)
The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
(*8)
Obtained when a DC reactor (DCR) is used.
(*9)
Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)
(*10)
The 55kW DC reactor (DCR) is optional with HD spec, and is provided as a standard accessory with LD spec.