Standard Specifications Basic type

Three-phase 200V series

LD (Low Duty) spec for light load
Item
Specifications
Type (FRN□□□G1S-2□)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Nominal applied motor [kW] (*1)
-
-
-
-
-
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Output ratings Rated capacity [kVA] (*2)
-
-
-
-
-
11
16
20
25
30
43
55
68
81
107
131
158
Rated voltage [V] (*3)
-
Three-phase 200 to 240V (with AVR)
Three-phase 200 to 230V (with AVR)
Rated Current [A] (*4)
-
-
-
-
-
31.8
(29)
46.2
(42)
59.4
(55)
74.8
(68)
88
(80)
115
(107)
146
180
215
283
346
415
Overload capability
-
120% for 1min
Rated frequency [Hz]
-
50, 60Hz
Input ratings Main circuit power
Phases, voltage, frequency
-
Three-phase 200 to 240V, 50/60Hz
Three-phase 200 to 220V, 50Hz
Three-phase 200 to 230V, 60Hz
Auxiliary control power input
Phases, voltage, frequency
-
Single-phase 200 to 240V, 50/60Hz

Single-phase 200 to 230V, 50/60Hz
Auxiliary power input for fan
Phases, voltage, frequency (*5)
-
-
Single-phase 200 to 220V, 50Hz
Single-phase 200 to 230V, 60Hz
Voltage, frequency variations
-
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5%
Rated current [A] (*7) with DCR
-
-
-
-
-
28.8
42.2
57.6
71.0
84.4
114
138
167
203
282
334
410
without DCR
-
-
-
-
-
42.7
60.7
80.1
97.0
112
151
185
225
270
-
-
-
Required power supply capacity [kVA] (*8)
with DCR
-
-
-
-
-
10
15
20
25
30
40
48
58
71
98
116
143
Braking Torque [%] (*9)
-
70%
15%
7 to12%
Braking transistor
-
Built-in
-
Min. ohmic value[Ω]
Torque [%]
-
16
130%
12
120%
8
130%
6
140%
4
150%
4
130%
-
Built-in braking resistance
-
20Ω
-
Braking time[s]
-
3.7s
3.4s
-
%ED
-
2.2
1.4
-
DC injection braking
-
Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 80%
DC reactor (DCR) (*10)

-
Optional
Standard accessory
Applicable safety standards
-
UL508C, C22.2No.14 (pending), EN61800-5-1:2003
Enclosure (IEC60529)
-
IP20 (IEC60529) closed type, UL open type(UL 50)
IP00 open type, UL open type
Cooling method
-
Fan cooling
Weight/Mass [kg]
-
6.5
6.5
5.8
9.5
9.5
10
25
32
42
43
(*1)
Fuji's 4-pole standard motor.
(*2)
Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.
(*3)
Output voltage cannot exceed the power supply voltage.
(*4)
When using the inverter in the ambient temperature of 40°C or over and with carrier frequency at 3kHz or higher, adjust the current under continuous running to be the value in ( ) or lower by controlling the load.
(*5)
The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)
(*6)
Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.
(*7)
The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
(*8)
Obtained when a DC reactor (DCR) is used.
(*9)
Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)
(*10)
The 55kW DC reactor (DCR) is optional with HD spec, and is provided as a standard accessory with LD spec.