Item |
Specifications |
Type (FRN□□□G1E-4E) |
90 |
110 |
132 |
160 |
200 |
220 |
280 |
315 |
355 |
400 |
Nominal applied motor [kW] (*2) |
110 |
132 |
160 |
200 |
250 |
250 |
315 |
355 |
400 |
450 |
Output ratings |
Rated capacity [kVA] (*3)
|
160 |
192 |
231 |
287 |
356 |
356 |
445 |
495 |
563 |
640 |
Rated voltage [V] (*4) |
Three-phase 380 to 480 V (with AVR function) |
Rated Current [A] |
210 |
253 |
304 |
377 |
468 |
468 |
585 |
650 |
740 |
840 |
Overload capability |
150% for 1 min |
Input ratings |
Voltage, frequency |
Three-phase 380 to 440 V, 50 Hz
Three-phase 380 to 480 V, 60 Hz
|
Voltage, frequency variations |
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) (*6), Frequency: +5 to -5% |
Required capacity with DCR [kVA] (*7) |
140 |
165 |
199 |
248 |
271 |
308 |
388 |
436 |
489 |
547 |
Braking |
Torque [%] (*8)
|
10 to 15% |
Braking transistor
|
- |
EMC filter
|
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004) |
DC reactor (DCR)
|
Option (*9) |
Applicable safety standards
|
UL508C, C22.2 No.14, EN50178:1997 |
Enclosure (IEC60529)
|
IP00, UL open type
|
Cooling method
|
Fan cooling |
Weight/Mass [kg] |
62 |
64 |
103 |
103 |
144 |
144 |
|
|
|
|
|
|
|
|
(*2) |
Fuji 4-pole standard motor |
(*3) |
Rated capacity is calculated by assuming the output rated voltage as 220V for 200V series and 440V for 400V series. |
(*4) |
Output voltage cannot exceed the power supply voltage. |
(*6) |
Voltage unbalance[%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V]×67(See IEC61800-3.) If this value is 2 to 3 %, use an optional AC reactor (ACR). |
(*7) |
Required when a DC reactor (DCR) is used. |
(*8) |
Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.) |
(*9) |
A DC reactor (DCR) is an option. However, inverters with a capacity of 75 kW or above require a DCR to be connected. Be sure to connect it to those inverters. |
|
|