Standard Specifications Basic type

Three-phase 400V series

(75 to 630kW)  HD (High Duty) spec for heavy load
Item
Specifications
Type (FRN□□□G1S-4□)
75
90
110
132
160
200
220
280
315
355
400
500
630
Nominal applied motor [kW] (*1)
75
90 110 132
160
200
220
280
315
355
400
500
630
Output ratings Rated capacity [kVA] (*2)
114 134 160 192 231 287 316 396 445 495 563 731 891
Rated voltage [V] (*3)
Three-phase 380 to 480V (with AVR)
Rated Current [A] 150 176 210 253 304 377 415 520 585 650 740 960 1170
Overload capability
150% for 1min, 200% for 3.0s
Rated frequency [Hz]
50, 60Hz
Input ratings Main circuit power
Phases, voltage, frequency
Three-phase 380 to 480V, 50Hz
Three-phase 380 to 480V, 60Hz
Auxiliary control power input
Phases, voltage, frequency
Single-phase 380 to 480V, 50/60Hz
Auxiliary power input for fan
Phases, voltage, frequency (*5)
Single-phase 380 to 440V, 50Hz
Single-phase 380 to 480V, 60Hz
Voltage, frequency variations
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5%
Rated current [A] (*7) with DCR 138 164 210 238 286 357 390 500 559 628 705 881 1115
without DCR
-
-
-
-
-
-
-
-
-
-
-
-
-
Required power supply capacity [kVA] (*8)

with DCR 96 114 140 165 199 248 271 347 388 436 489 611 773
Braking Torque [%] (*9)
10 to 15%
Braking transistor
-
Min. ohmic value [Ω]
Torque [%]
-
DC injection braking Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 100%
DC reactor (DCR) (*10)
Standard accessory
Applicable safety standards
UL508C, C22.2No.14 (pending), EN61800-5-1:2003
Enclosure (IEC60529)
IP20(IEC60529) closed type, UL open type (UL 50)
Cooling method
Fan cooling
Weight/Mass [kg]
42
                       
(*1)
Fuji's 4-pole standard motor
(*2)
Rated capacity is calculated by assuming the output rated voltage as 220V for three-phase 200V series and 440V for three-phase 400V series.
(*3)
Output voltage cannot exceed the power supply voltage.
(*5)
The auxiliary power input is used as an AC fan power input when combining the unit such as high power factor PWM converter with power regenerative function. (Generally not used.)
(*6)
Interphase voltage unbalance ratio[%] = (max. voltage [V] - min. voltage [V])/3-phase average voltage [V]×67(See IEC61800-3.) Use the DC reactor (ACR: optional) when used with 2 to 3 % of unbalance ratio.
(*7)
The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
(*8)
Obtained when a DC reactor (DCR) is used.
(*9)
Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)
(*10)
The 55kW DC reactor (DCR) is optional with HD spec, and is provided as a standard accessory with LD spec.