Energy savings with inverter

Sample energy saving data

Exhaust fan (generating variable torque load)

Motor capacity and inverter capacity

· Motor capacity : 22(kW)
· Inverter model : FRN22F1S-2 (FRENIC-Eco)
· DC REACTOR : DCR2-22A

Power reduction rate and energy saving effect amount

Item Operation using commercial power Inverter-controlled operation
Operation frequency (Hz) 50 45 40 35
Average power use (kW) 17.2 13.1 9.10 6.23
Power reduction rate (%) - up30.7 up47.1 up63.8
Annual power charge (yen) 1,574,006 1,198,807 832,759 570,120
Annual amount (yen) of energy saving effect - 375,199 741,247 1,003,886
Annual CO2 reduction volume (kg/year) - 3,660 7,232 9,794

Operating conditions

· Annual operating days : 310 (days/year)
· Working hours per day : 24 (hrs/day)
· Power charge unit price : 12.3 (yen/kWh)

Cooling tower (generating variable torque load)

Motor capacity and inverter capacity

· Motor capacity : 5.5 (kW)
· Inverter model : FRN5.5F1S-2 (FRENIC-Eco)
· DC REACTOR : DCR2-5.5

Power reduction rate and energy saving effect amount

Item Operation using commercial power Inverter-controlled operation
Operation frequency (Hz) 60 45 40 35
Average power use (kW) 5.18 2.31 1.63 1.10
Power reduction rate (%) - up55.4 up68.5 up78.8
Annual power charge (yen) 410,256 182,952 129,096 87,120
Annual amount (yen) of energy savings effect - 227,304 281,160 323,136
Annual CO2 reduction volume (kg/year) - 2,066 2,556 2,938

Operating conditions

· Annual operating days : 300 (days/year)
· Working hours per day : 20 (hrs/day)
· Power charge unit price : 13.2 (yen/kWh)

Mist collector (generating variable torque load)

Motor capacity and inverter capacity

· Motor capacity : 3.7 (kW)
· Inverter model : FRN3.7F1S-2 (FRENIC-Eco)
· DC REACTOR : DCR2-3.7

Power reduction rate and energy saving effect amount

Item Operation using commercial power Inverter-controlled operation
Operation frequency (Hz) 60 45 40 35
Average power use (kW) 3.27 1.44 0.99 0.69
Power reduction rate (%) - up56.0 up69.7 up78.9
Annual power charge (yen) 260,161 114,566 78,764 54,896
Annual amount (yen) of energy savings effect - 145,595 181,397 205,265
Annual CO2 reduction volume (kg/year) - 1,142 1,423 1,610

Operating conditions

· Annual operating days : 260 (days/year)
· Working hours per day : 20 (hrs/day)
· Power charge unit price : 15.3 (yen/kWh)

Conduct a search. You can study energy savings with the following types of equipment.

Fan systems
  • Air conditioning fans
  • AHU
  • Dust collectors
  • Mist -collectors
  • Exhaust fans
  • Package air conditioners, etc.
Pump systems
  • Cooling water pumps
  • Circulating pumps
  • Cleaning pump
  • Roots blowers
  • Coolant pumps
  • Water cooler pumps, etc.

Page Top