OPCN-1 communication unit (UG03I-J) |
 |
Item |
Specification |
Transmission method |
Half-duplex, synchronous system |
Transmission rate/ Transmission distance (switchable) *1 |
125kbps/1000m, 250kbps/800m 500kbps/480m, 1Mbps/240m |
No. of connected stations *2 |
1 to 31 (max.) |
Connection method |
M3.5 screw terminal block |
Applicable cable |
Twisted-pair cable with shielding |
Transmission content |
GET/PUT service, I/O service |
Station No. |
01 to 7F (Rotary switch) |
|
 |
Notes: |
PLCs and interface units for connection with the OPCN-1 communication unit are as follows: |
|
- OPCN-1 interface master module (NP1L-JP1) for Fuji MICREX-SX SPH
- OPCN-1 interface master module (NJ-JPCN-1) for Fuji FLEX-PC NJ series
- JPCN-1 interface master module (AJ71J92-S3, A1SJ71J92-S3) for Mitsubishi MELSEC A series
- J-NET module (LWE580, LQE040) for Hitachi HIDIC-S10a series, S10min
- JPCN unit (C200HW-JRM21) for Omron SYSMAC C200H series
|
|
|
*1 |
The transmission distance indicates an example when Furukawa-made cable (KPEV-SB 1.25mm2) is used. Note that the length may change depending on the cable characteristics. |
*2 |
The number of PODs that can be connected varies depending on such factors as application and PLC. When connecting three or more PODs (including message communication devices) to a single PLC, use I/O communication to connect the PODs to the PLC. |
|
 |
SX bus communication unit (UG03I-S,UG230I-S) |
 |
Item |
Specification |
Transmission line |
Dedicated cable *1 (total length 25m) |
No. of connected stations |
No. of PODs connected via SX bus in same configuration: 8 |
Transmission rate |
25Mbps |
PLC connecting range |
CPUs in same configuration |
|
 |
*1 |
For connection, use the following SX bus extension cable. |
|
 |
Type |
Cable length (unit: mm) |
NP1C-P3 |
300 |
NP1C-P6 |
600 |
NP1C-P8 |
800 |
NP1C-02 |
2,000 |
NP1C-05 |
5,000 |
NP1C-10 |
10,000 |
NP1C-25 |
25,000 |
|
 |
For UG03I-S, mount the ferrite core that is supplied with the SX bus cable. |
 |
Ethernet (FL-net) communication unit (UG03I-E2) |
 |
Item |
Specification |
AUI |
10BASE-T |
10BASE5 |
10BASE2 |
Transmission rate |
10Mbps |
Transmission method |
Base band |
Transmission protocol (FL-net) |
FA-link protocol |
Max. network length or max. node distance |
2500m (5 segments) |
925m (5 segments) |
500m (HUB: 4 stages) |
Max. segment length |
500m |
185m |
100m between node and HUB |
Max. number of nodes per system |
254 stations (not via rooter) |
Max. number of nodes |
100 units/ segment |
30 units/ segment |
2 units/ segment |
Min. node distance |
2.5m |
0.5m |
None |
Connecting cable |
Ethernet Coaxial cable (50Ω) |
RG58A/U, RG58C/U Coaxial cable (50Ω) |
UTP (Twisted-pair cable without shielding) 22-26AWG |
|
 |
Notes: |
With UG03I-E2, Ethernet and FL-net communication is possible. |
|
 |
DeviceNet communication unit(UG03I-D) |
 |
Item |
Specification |
Vendor ID |
319 |
Product code |
7521(HEX) |
Connector type |
Screw connector |
Input/Output specifications |
Conforms to DeviceNet protocol |
Max, number of connected stations |
63 |
Transmission rate |
125K/250K/500Kbps(changeable with the dip switch) |
Transmission distance |
Transmission rate |
Max.network lenght |
Branch line length |
Total branch line length |
THICK
cable |
THIN
cable |
125Kbps |
500m |
100m |
6m |
156m |
250Kbps |
250m |
100m |
6m |
78m |
500Kbps |
100m |
100m |
6m |
39m |
Communication function |
I/O messages:Polling |
|
|
|
 |
T-link communication unit (UG03I-T,UG230I-T) |
 |
Item |
Specification |
Transmission method |
Half-duplex serial transmission 1:N (polling/selecting) |
Transmission rate |
500kbps |
Transmission distance *1 |
1km |
No. of connected stations *2 |
1 to 32 (max.) |
Connection method |
M3.5 screw terminal |
Applicable cable |
Twisted-pair cable with shielding |
Number of words occupied |
2, 4, 8, 16, 64 words (by setting) |
Station No. |
00 to 98 (hardware switch) |
|
 |
*1 |
For cable types, see User Manual <T-Link Communications> (FEH356). |
*2 |
The number of PODs that can be connected varies depending on such factors as application and PLC. When connecting four or more PODs (including message communication devices) to a single PLC, use I/O communication to connect the PODs to the PLC |
 |
PROFIBUS-DP communication unit (UG03I-P) |
 |
Item |
Specification |
No. of connected stations |
Slave stations: 125 (max.) |
Station No. setting range |
1 to 125 (set by the editor) |
Type of transmission line |
Bus structure (multi-drop) |
Transmission line *1 |
Bus transmission line: twisted-pair cable with shielding (Total length depends on transmission rate.) |
Transmission method |
Half-duplex, serial transmission conforming to EIA RS-485 |
Communication setting |
Data length: 8 bits Parity: Even Stop bit: 1 |
Transmission rate (bps) |
9600 |
19200 |
93750 |
187500 |
500000 |
1.5M |
12M |
Transmission distance (m) |
1200 |
1200 |
1200 |
1000 |
400 |
200 |
100 |
Coding scheme |
NRZ (Non Return to Zero) system |
Occupied input/output points |
Input/output: 1 to 48 words (32/64/96 bytes are selected from the editor)
|
|
 |
Note: |
When connecting with the PROFIBUS-DP communication unit, use Siemens SIMATIC S7 series PLC. |
*1 |
For cable types, see User Manual <PROFIBUS Communications> (FEH368). |
|
 |
CC-Link communication unit (UG03I-C) |
 |
Item |
Specification |
Transmission rate/ Max. transmission distance *1 |
156kbps/1200m, 625kbps/600m, 2.5Mpbs/200m, 5Mbps/150m, 10Mbps/100m |
Maximum No. of connected stations *2 |
26 (intelligent device stations) |
No. of occupied stations |
1 or 4 (changeable with the DIP switch) |
Transmission method |
Polling system |
Synchronization |
Frame synchronization system |
Coding scheme |
NRZI (Non Return to Zero Inverted) system |
Type of transmission line |
Bus (RS-485) |
Transmission format |
Conforms to HDLC |
Error control system |
CRC |
Connecting cable *3 |
Twisted-pair cable with shielding |
|
 |
Notes: |
PLCs and interface units for connection with CC-Link communication unit are as follows: |
|
- CC-Link interface master-local unit (AJ61BT11, A1SJ61BT11) for Mitsubishi MELSEC A series. - CC-Link interface master-local unit (AJ61QBT11, A1SJ61QT11) for MELSEC QnA |
|
|
*1 |
Irrespective of transmission rate setting, 2m or longer cable length is necessary between the POD and adjacent stations.
|
*2 |
The number of PODs that can be connected varies depending on such factors as application and PLC. When connecting four or more PODs (including message communication devices) to a single PLC, use I/O communication to connect the PODs to the PLC. |
*3 |
For cable types, see User Manual <CC-Link Communications> (FEH355). |
|
|