DC 1000-V Central Inverter
Item |
Weries name |
PVI1000BT-3P/1000-F |
Remarks |
Rated output |
1000 kVA |
Insulation system |
Transformerless system |
Electric specifications (DC input) |
DC input voltage range |
1000 V |
|
DC input voltage (MPPT range) |
570 V to 850 V |
|
Number of DC input branches |
4 |
16 as an option |
Electric specifications (AC output) |
Rated output capacity |
1000 kVA/900 kW |
|
Rated output voltage |
380 V |
|
Rated frequency |
50/60 Hz |
|
Number of output phases |
Three-phase, three-wire; isolated neutral system supported. |
|
Rated output current |
1519 A |
|
Output power factor |
0.99 or less (at rated output) |
|
Output current distortion (total) |
5 % or less |
at rated output,upto 40th |
Output current distortion (each) |
3 % or less |
at rated output,upto 40th |
Maximum efficiency |
98.5 % |
|
Maximum (Euro efficiency) |
98.3 % |
|
Overload capacity |
100 % continuous |
|
Noise |
80 dB |
At rated |
System interconnection |
System protection |
OV, UV, OF, UF |
|
Islanding detection (passive) |
Detection of voltage phase jump |
|
Islanding detection (active) |
Frequency feedback method with step injection |
|
Voltage rise suppression function |
Reactive current compensation, active current output suppression |
|
FRT |
According to PEA regulation |
|
Panel structure |
Installation system |
Outdoor self-standing type |
Measures against salt damage are optional. |
Applicable IP |
IP54 |
|
Cable lead-in |
Bottom |
|
Cooling system |
Forced-air cooling&heat exchanger colling |
|
Dimensions (W × D × H) |
2000×950×1950 mm |
|
Mass |
1800 kg |
|
Environmental conditions |
Ambient temperature for operation |
−5°C to +50°C |
Power is conserved when operating at temperatures above 42°C. |
Relative humidity |
15 to 95 % |
Non-condensing |
Altitude |
up to 2000m |
|
Relevant standard |
2016,PEA regulation authentication |
|
Communication system |
RS-485 |
|
DC 1500-V Central Inverter
Item |
Specifications |
Remarks |
General |
Type number |
PVI1500CJ-3/2500 |
|
Rated output power |
2500 kVA |
|
Insulation system |
No isolation transformer inside the inverter |
|
Electric specifications (DC input) |
DC input voltage (Max.) |
DC 1500 V |
|
DC input voltage (operation) |
DC 915 to 1350 V |
|
Number of DC input branches |
24 |
MPPT: 1 |
Electric specifications (AC output) |
Rated output power |
2500 kVA |
|
Rated output voltage |
AC 590 V |
|
Rated frequency |
50/60 Hz |
|
Number of output phases |
Three-phase and three-wire |
Earthing on AC side is impossible |
Rated output current |
2447 A |
|
Output power factor |
Lead 0.8 to Lag 0.8 |
Set increment: 0.01 |
Output current distortion factor (total) |
5% or less |
at rated output power, upto 40th |
Output current distortion factor (each) |
3% or less |
at rated output power, upto 40th |
Maximum efficiency |
98.6% |
It does not include control power source, and is shown with efficiency tolelance according to IEC 61683 |
Euro efficiency |
98.4% |
Overload capacity |
100% |
|
Noise |
Not higher than 80 dB |
|
System interconnection |
System protection |
(OVR, UVR, OFR, UFR) |
|
Islanding detection (passive) |
Detection of voltage phase jump |
|
Islanding detection (active) |
Frequency feedback method with step injection |
|
Voltage rise suppression function |
Reactive current compensation, active current output suppression |
|
FRT |
JEA9701-2019, PEA 2016 |
|
Panel structure |
Installation system |
Outdoor |
|
Applicable IP |
IP55 |
|
Cable lead-in |
Bottom |
|
Cooling system |
Forced Air cooling, Heat exchanger cooling |
|
Dimensions (W × D × H) |
2100 × 1300 × 2480 mm |
|
Mass |
4000 kg |
|
Environmental conditions |
Ambient temperature for operation |
-10 to +60℃ |
|
Relative humidity |
4 to 100% |
Without condensation |
Altitude |
Up to 1000 m |
|
Relevant standard |
IEC 62109-1, -2, PEA 2016, IEC 61727, JEA9701-2019 |
|
Communication system |
RS485 |
Option: Ethernet |
-
*
-
This product is released in October 2019. The specifications can be changed without any notice.
String Inverter
Item |
Specifications |
Remarks |
General |
Type number |
PIS-50/500-T |
PIS-36/380-G |
PIS-39/415-G |
|
Rated output power |
47.5 kVA |
36 kVA |
39 kVA |
|
Insulation system |
No isolation transformer inside the inverter |
|
Electric specifications (DC input) |
DC input voltage (Max.) |
DC 1100 V |
|
DC input voltage (operation) |
DC 200 to 1000 V |
Nominal power range:
625~850V |
Number of DC input branches |
8 |
MPPT: 4 |
Electric specifications (AC output) |
Rated output power |
47.5 kVA |
36 kVA |
39 kVA |
|
Rated output voltage |
AC 500 V |
AC 380 V |
AC 415 V |
|
Rated frequency |
50 Hz |
50/60 Hz |
|
Number of output phases |
Three-phase and three-wire |
Earthing on AC side is impossible |
Rated output current |
55 A |
Maximum 110% |
Output power factor |
Lead 0.8 to Lag 0.8 |
Set increment: 0.001 |
Output current distortion factor (total) |
5% or less |
During nominal output power, 40th |
Output current distortion factor (each) |
3% or less |
During nominal output power, 40th |
Conversion efficiency (Max.) |
99.0% |
98.6% |
98.7% |
With efficiency tolelance according to IEC 61683 |
Conversion efficiency (Euro) |
98.5% |
98.1% |
98.2% |
|
Overload capacity |
110% |
|
Noise |
Not higher than 65 dB |
|
System interconnection |
System protection |
(OVR, UVR, OFR, UFR) |
|
Islanding detection (passive) |
Detection of voltage phase jump |
|
Islanding detection (active) |
Frequency feedback method with step injection |
|
Voltage rise suppression function |
Reactive current compensation, active current output suppression |
|
FRT |
GB/T 19964-2012, JEA9701-2019, PEA 2016 |
|
Panel structure |
Installation system |
Outdoor |
|
Applicable IP |
IP65 |
|
Cable lead-in |
Bottom |
|
Cooling system |
Natural air cooling |
|
Dimensions (W × D × H) |
930 × 260 × 540 mm |
|
Mass |
58 kg |
|
Environmental conditions |
Ambient temperature for operation |
-25 to +60℃ |
|
Relative humidity |
4 to 100% |
Without condensation |
Altitude |
Up to 1000 m |
|
Relevant standard |
NB/T 32004-2013, GB/T 19964-2012, PEA 2016, IEC 61727, IEC 61683, JEA9701-2019 |
|
Communication system |
RS485 |
|
-
*
-