| Type FRN□VG7S-2 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |
| Nominal applied motor [kW] | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |
| Rated capacity [kVA] (*1) | 1.9 | 3.0 | 4.1 | 6.8 | 10 | 14 | 18 | 24 | 28 | 34 | 44 | 55 | 68 | 81 | 107 | 131 | |
| Rated current (Continuous) (1min.) |
5 | 8 | 11 | 18 | 27 | 37 | 49 | 63 | 74 | 90 | 116 | 145 | 180 | 215 | 283 | 346 | |
| 7.5 | 12 | 16.5 | 27 | 40.5 | 55.5 | 73.5 | 94.5 | 111 | 135 | 174 | 217.5 | 270 | 333 | 441 | 519 | ||
| Phase, Voltage, Frequency | 3-phase 200 to 230V, 50Hz/60Hz | 3-phase 200 to 220V/50Hz, 200 to 230V/60Hz (*2) | |||||||||||||||
| Voltage/frequency variation | Voltage: +10 to -15%, Frequency: +5 to -5%, Voltage unbalance: 2% or less (*3) | ||||||||||||||||
| Momentary voltage dip capability (*4) |
When voltage drops from the rated voltage, the inverter will continue operation if the voltage is more than 165V. If the voltage is less than 165V, the inverter can be operated for 15ms. |
||||||||||||||||
| Rated current [A] (with DCR) (*7) (without DCR) |
3.1 | 5.7 | 8.3 | 14.0 | 19.7 | 26.9 | 39.0 | 54.0 | 66.2 | 78.8 | 109 | 135 | 163 | 199 | 272 | 327 | |
| 6.4 | 11.1 | 16.1 | 25.5 | 40.8 | 52.6 | 76.9 | 98.5 | 117 | 136 | 168 | 204 | 243 | 291 | - | - | ||
| Required power supply capacity [kVA] (*5) | 1.1 | 2.0 | 2.9 | 4.9 | 6.9 | 9.4 | 14 | 19 | 23 | 28 | 38 | 47 | 57 | 69 | 95 | 114 | |
| Braking method /braking torque | Braking resistor discharge control: 150% braking torque, Separately installed braking resistor (option), Separately installed braking unit (option for 75kW or more) |
||||||||||||||||
| Carrier frequency [kHz] (*6) | 0.75 to 15 | 0.75 to 10 | |||||||||||||||
| Mass [kg] |
8 | 8 | 8 | 8 | 8 | 8 | 12.5 | 12.5 | 25 | 25 | 30 | 37 | 46 | 48 | 70 | 115 | |
| Enclosure | Up to 15kW: IP20, 18.5kW or over: IP00 (IP20: option) | ||||||||||||||||
*1) Inverter output capacity [kVA] at 220V.
*2) Order individually for 220 to 230V/50Hz.
*3) Use a DC REACTOR if the voltage unbalance exceeds 2% (this is the same as for FUJI's conventional models).
Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] × 67
*4) Tested at the standard load condition (85% load of nominal applied motor) prescribed by JEMA.
*5) When power-factor correcting DC REACTOR is used. (Optional for 55kW or less model)
*6) The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
*7) This value is obtained by using a FUJI original calculation method.
*8) Use the function code F80 to switch between CT, VT and HT uses.
*9) Not EN standard conformed.
*1) Inverter output capacity [kVA] at 440V.
*2) Use a DC REACTOR if the voltage unbalance exceeds 2% (this is the same as for FUJI's conventional models).
Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] × 67
*3) Tested at the standard load condition (85% load of nominal applied motor) prescribed by JEMA.
*4) When power-factor correcting DC REACTOR is used. (Optional for 55kW or less model)
*5) The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
*6) This value is obtained by using a FUJI original calculation method.
*7) Use the function code F80 to switch between CT, VT and HT uses.
*8) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, a connector inside the inverter must be switched.
When the input voltage is 380Hz, the power output may be occasionally reduced.For the detail, refer to the user's manual of "FRENIC 5000 VG7S".
(described in 11.5 Characteristic combination list)
*9) The inverter for 18.5kW and 250kW motor does not conform to EN standards.If a standard-compliant model is required, select the inverter for 22kW and 280kW.