
In principle, the guideline applies to the customers that meet the following two conditions:
The level (calculated value) of the harmonic current that flows from the customer's receiving point out to the system is subjected to the regulation. The regulation value is proportional to the contract demand. The regulation values specified in the guideline are shown in Table 1.
Table 1 Upper limits of harmonic outflow current per kW of contract demand [mA/kW]
| Receiving voltage | 5th | 7th | 11th | 13th | 17th | 19th | 23th | Ove r25th |
| 6.6kV | 3.5 | 2.5 | 1.6 | 1.3 | 1.0 | 0.90 | 0.76 | 0.70 |
| 22kV | 1.8 | 1.3 | 0.82 | 0.69 | 0.53 | 0.47 | 0.39 | 0.36 |
Although the equivalent capacity (Pi) is calculated using the equation of (input rated capacity) x (conversion factor), catalog of conventional inverters do not contain input rated capacities. A description of the input rated capacity is shown below:
(1) "Inverter rated capacity" corresponding to "Pi"Table 2 "Input rated capacities" of general-purpose inverters determined by the nominal applied motors
| Nominal applied motor [kW] | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |
| Pi [kVA] |
200V | 0.57 | 0.97 | 1.95 | 2.81 | 4.61 | 6.77 | 9.07 | 13.1 | 17.6 | 21.8 | 25.9 |
| 400V | 0.57 | 0.97 | 1.95 | 2.81 | 4.61 | 6.77 | 9.07 | 13.1 | 17.6 | 21.8 | 25.9 | |
| Nominal applied motor [kW] | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 200 | 220 | |
| Pi [kVA] |
200V | 34.7 | 42.8 | 52.1 | 63.7 | 87.2 | 104 | 127 | ||||
| 400V | 34.7 | 42.8 | 52.1 | 63.7 | 87.2 | 104 | 127 | 153 | 183 | 229 | 252 | |
| Nominal applied motor [kW] | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 530 | 560 | 630 | |
| Pi [kVA] |
200V | ||||||||||
| 400V | 286 | 319 | 359 | 405 | 456 | 512 | 570 | 604 | 638 | 718 | |
Table 3 "Conversion factors Ki" for general-purpose inverters determined by reactors
| Circuit category | Circuit type | Conversion factor Ki | Main applications | |
| 3 | Three-phase bridge 3 (capacitor smoothing) |
Without a reactor | K31=3.4 | • General-purpose inverters • Elevators • Refrigerators, air conditioning systems • Other general appliances |
| With a reactor (ACR) |
K32=1.8 | |||
| With a reactor (DCR) |
K33=1.8 | |||
| With reactors (ACR and DCR) |
K34=1.4 | |||
Table 4 "Input fundamental currents" of general-purpose inverters determined by the nominal applied motors
| Nominal applied motor [kW] | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |
| Input fundamental current [A] |
200V | 1.62 | 2.74 | 5.50 | 7.92 | 13.0 | 19.1 | 25.6 | 36.9 | 49.8 | 61.4 | 73.1 |
| 400V | 0.81 | 1.37 | 2.75 | 3.96 | 6.50 | 9.55 | 12.8 | 18.5 | 24.9 | 30.7 | 36.6 | |
| 6.6 kV converted value [mA] | 49 | 83 | 167 | 240 | 394 | 579 | 776 | 1121 | 1509 | 1860 | 2220 | |
| Nominal applied motor [kW] | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 200 | 220 | |
| Input fundamental current [A] |
200V | 98.0 | 121 | 147 | 180 | 245 | 293 | 357 | ||||
| 400V | 49.0 | 60.4 | 73.5 | 89.9 | 123 | 147 | 179 | 216 | 258 | 323 | 355 | |
| 6.6 kV converted value [mA] | 2970 | 3660 | 4450 | 5450 | 7450 | 8910 | 10850 | 13090 | 15640 | 19580 | 21500 | |
| Nominal applied motor [kW] | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 530 | 560 | 630 | |
| Input fundamental current [A] |
200V | ||||||||||
| 400V | 403 | 450 | 506 | 571 | 643 | 723 | 804 | 852 | 900 | 1013 | |
| 6.6 kV converted value [mA] | 24400 | 27300 | 30700 | 34600 | 39000 | 43800 | 48700 | 51600 | 54500 | 61400 | |
Table 5 Generated harmonic current [%], 3-phase bridge (capacitor smoothing)
| Degree | 5th | 7th | 11th | 13th | 17th | 19th | 23th | 25th |
| Without a reactor | 65 | 41 | 8.5 | 7.7 | 4.3 | 3.1 | 2.6 | 1.8 |
| With a reactor (ACR) | 38 | 14.5 | 7.4 | 3.4 | 3.2 | 1.9 | 1.7 | 1.3 |
| With a reactor (DCR) | 30 | 13 | 8.4 | 5.0 | 4.7 | 3.2 | 3.0 | 2.2 |
| With reactors (ACR and DCR) | 28 | 9.1 | 7.2 | 4.1 | 3.2 | 2.4 | 1.6 | 1.4 |
n nth harmonic current [A] = Fundamental current [A] x 
Calculate the harmonic current of each degree using the following equation:
Table 6 Availability factors of inverters, etc. for building equipment (standard values)
| Equipment type | Inverter capacity category | Single inverter availability factor |
| Air conditioning system | 200kW or less | 0.55 |
| Over 200kW | 0.60 | |
| Sanitary pump | - | 0.30 |
| Elevator | - | 0.25 |
| Refrigerator, freezer | 50kW or less | 0.60 |
| UPS (6-pulse) | 200kVA | 0.60 |
[Correction coefficient according to contract demand level]
ï Since the total availability factor decreases with increase in the building scale, calculating reduced harmonics with the correction coefficient s defined in Table 7 below is permitted.
Table 7 Correction coefficient according to the building scale
| Contract demand [kW] | Correction coefficient b |
| 300 | 1.00 |
| 500 | 0.90 |
| 1000 | 0.85 |
| 2000 | 0.80 |
*If the contract demand is between two specified values shown in Table 7, calculate the value by interpolation.
Calculate only the "5th and 7th" harmonic currents
Copyright (c) 2007 Fuji Electric FA Components & Systems Co.,Ltd. All rights reserved.