| Type FRN□VG7S-2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
| Nominal applied motor [kW] | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
| Rated capacity [kVA] (*1) | 6.8 | 10 | 14 | 18 | 24 | 28 | 34 | 44 | 55 | 68 | 81 | |
|
Rated current (*2) (1min.) (10s) |
18 | 27 | 37 | 49 | 63 | 74 | 90 | 116 | 145 | 180 | 215 | |
| 27 | 40.5 | 55.5 | 73.5 | 94.5 | 111 | 135 | 174 | 217.5 | 270 | 333 | ||
| 32.4 | 45.7 | 63.3 | 85.8 | 111 | 142 | 170 | 194 | 246 | 290 | 360 | ||
| Phase, Voltage, Frequency | 3-phase 200 to 230V, 50Hz/60Hz | 3-phase 200 to 220V/50Hz, 200 to 230V/60Hz (*3) | ||||||||||
| Voltage/frequency variation | Voltage: +10 to -15%, Frequency: +5 to -5%, Voltage unbalance: 2% or less (*4) | |||||||||||
| Momentary voltage dip capability (*5) | When voltage drops from the rated voltage, the inverter will continue operation if the voltage is more than 165V. If the voltage is less than 165V, the inverter can be operated for 15ms. | |||||||||||
| Rated current [A] (with DCR) (*8) (without DCR) |
14.0 | 19.7 | 26.9 | 39.0 | 54.0 | 66.2 | 78.8 | 109 | 135 | 163 | 199 | |
| 25.5 | 40.8 | 52.6 | 76.9 | 98.5 | 117 | 136 | 168 | 204 | 243 | 291 | ||
| Required power supply capacity [kVA] (*6) | 4.9 | 6.9 | 9.4 | 14 | 19 | 23 | 28 | 38 | 47 | 57 | 69 | |
| Carrier frequency [kHz] (*7) | 0.75 to 15 | |||||||||||
| Mass [kg] | 8 | 8 | 8 | 12.5 | 12.5 | 25 | 25 | 30 | 37 | 46 | 48 | |
| Enclosure | Up to 15kW: IP20, 18.5kW or over: IP00 (IP20: option) | |||||||||||
| Continuous [%] (*9) | 100% | |||||||||||
| 1min. rating [%] (*9) | 150% | |||||||||||
| 10s rating [%] (*9) | 200% (at 80% or less of rated speed)/170% (at rated speed) | 170% | ||||||||||
| Braking method/braking torque |
Braking resistor discharge control: 150% braking torque, Separately installed braking resistor (option) | |||||||||||
*1) Inverter output capacity [kVA] at 220V.
*2) Select the inverter capacity such that the square average current in cycle operation is 80% or less of the rated current of an inverter.
*3) Order individually for 220 to 230V/50Hz.
*4) Use a DC REACTOR if the voltage unbalance exceeds 2% (this is the same as for FUJI's conventional models).
Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] × 67
*5) Tested at the standard load condition (85% load of nominal applied motor) prescribed by JEMA.
*6) When power-factor correcting DC REACTOR (option) is used.
*7) The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
*8) This value is obtained by using a FUJI original calculation method.
*9) These torque characteristics are obtained when combined with a dedicated motor.
*10) Use the function code F80 to switch between CT, VT and HT uses.
*11) Not EN standard conformed.
| Type FRN□VG7S-2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
| Nominal applied motor [kW] | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
| Rated capacity [kVA] (*1) | 6.8 | 10 | 14 | 18 | 24 | 29 | 34 | 44 | 57 | 69 | 85 | |
|
Rated current (*2) (1min.) (10s) |
9.0 | 13.5 | 18.5 | 24.5 | 32.0 | 39.0 | 45.0 | 58.0 | 75.0 | 91.0 | 112 | |
| 13.5 | 20.0 | 27.5 | 36.5 | 48.0 | 58.5 | 67.5 | 90.0 | 113 | 137 | 168 | ||
| 16 | 22.7 | 31.6 | 42.9 | 59.1 | 73.5 | 85.1 | 96.0 | 120 | 150 | 182 | ||
| Phase, Voltage, Frequency | 3-phase 380 to 480V, 50Hz/60Hz | 3-phase 380 to 440V/50Hz, 380 to 480V/60Hz (*9) | ||||||||||
| Voltage/frequency variation | Voltage: +10 to -15%, Frequency: +5 to -5%, Voltage unbalance: 2% or less (*3) | |||||||||||
| Momentary voltage dip capability (*4) | When voltage drops from the rated voltage, the inverter will continue operation if the voltage is more than 310V. If the voltage is less than 310V, the inverter can be operated for 15ms. | |||||||||||
| Rated current [A] (with DCR) (*7) (without DCR) |
7.1 | 10 | 13.5 | 19.8 | 26.8 | 33.2 | 39.3 | 54 | 67 | 81 | 100 | |
| 14.9 | 21.5 | 27.9 | 39.1 | 50.3 | 59.9 | 69.3 | 86 | 104 | 124 | 150 | ||
| Required power supply capacity [kVA] (*5) | 5.0 | 7.0 | 9.4 | 14 | 19 | 24 | 28 | 38 | 47 | 57 | 70 | |
| Carrier frequency [kHz] (*6) | 0.75 to 15 | |||||||||||
| Mass [kg] | 8 | 8 | 8 | 12.5 | 12.5 | 25 | 25 | 30 | 35 | 40 | 41 | |
| Enclosure | Up to 15kW: IP20, 18.5kW or over: IP00 (IP20: option) | |||||||||||
| Continuous [%] (*8) | 100% | |||||||||||
| 1min. rating [%] (*8) | 150% | |||||||||||
| 10s rating [%] (*8) | 200% (at 80% or less of rated speed)/170% (at rated speed) | 170% | ||||||||||
| Braking method/braking torque |
Braking resistor discharge control: 150% braking torque, Separately installed braking resistor (option) | |||||||||||
*1) Inverter output capacity [kVA] at 440V.
*2) Select the inverter capacity such that the square average current in cycle operation is 80% or less of the rated current of an inverter.
*3) Use a DC REACTOR if the voltage unbalance exceeds 2% (this is the same as for FUJI's conventional models).
Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] × 67
*4) Tested at the standard load condition (85% load of nominal applied motor) prescribed by JEMA.
*5) When power-factor correcting DC REACTOR (option) is used.
*6) The inverter may automatically reduce carrier frequency in accordance with ambient temperature or output current in order to protect itself.
*7) This value is obtained by using a FUJI original calculation method.
*8) These torque characteristics are obtained when combined with a dedicated motor.
*9) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, a connector inside the inverter must be switched.
*10) Use the function code F80 to switch between CT, VT and HT uses.
*11) The inverter for 18.5kW motor does not conform to EN standards.
If a standard-compliant model is required, select the inverter for 22kW.
Copyright (c) 2007 Fuji Electric FA Components & Systems Co.,Ltd. All rights reserved.