Product Information ---Specifications
Standard specification Therr-phase 230V series Therr-phase 460V series Single-phase 230V series Common specifications
Standard specification
Three-phase 460V (1/2 to 20HP)
Item Specifications
Type (FRNE1S-4U) F50 001 002 003 005 007 010 015 020
Applicable motor rating [HP] (*1) 1/2 1 2 3 5 7.5 10 15 20
Output ratings Rated capacity [kVA] (*2) 1.2 2.0 2.9 4.4 7.2 10 14 19 24
Rated voltage [V] (*3) Three-phase 380V to 480V (with AVR function)
Rated current [A] (*4)
1.5 2.5 3.7 5.5 9.0 13 18 24 30
Overload capability 150% of rated current for 1min, 200% - 0.5s
Rated frequency [Hz] 50, 60Hz
input power Phases, voltage, frequency Three-phase, 380 to 480V, 50/60Hz
Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5%
Rated current [A] (*9) (with DCR) 0.85 1.6 3.0 4.4 7.3 10.6 14.4 21.1 28.8
(without DCR) 1.7 3.1 5.9 8.2 13.0 17.3 23.2 33.0 43.8
Required power supply capacity [kVA] (*5) 0.6 1.1 2.0 2.9 4.9 7.4 10 15 20
Braking Torque [%] (*6) 100 70 40 20
Torque [%] (*7) 150
DC injection braking Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 100% of rated current
Braking transistor Built-in
Applicable safety standards UL508C, C22.2No.14, EN50178:1997
Enclosure (IEC60529) IP20, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass [lbs(kg)] 2.4
(1.1)
2.6
(1.2)
3.7
(1.7)
3.7
(1.7)
5.1
(2.3)
7.5
(3.4)
7.9
(3.6)
13
(6.1)
16
(7.1)
(*1) Fuji's 4-pole standard motor
(*2) Rated capacity is calculated by assuming the output rated voltage as 230V for three-phase 230V series and 460V for three-phase 460V series.
(*3) Output voltage cannot exceed the power supply voltage.
(*4) When setting the carrier frequency (F26) to 3 kHz or less. Use the current ( ) or below when the carrier frequency setting is higher than 4kHz and continuously operating at 100%.
(*5) Obtained when a DC REACTOR is used.
(*6) Average braking torque obtained when reducing the speed from 60Hz with AVR control OFF (Varies with the efficiency of the motor.)
(*7) Average braking torque obtained by use of external braking resistor (standard type available as option)
(*8) Voltage unbalance [%] = x 67(IEC 61800-3)
If this value is 2 to 3%, use AC REACTOR (ACR: option).
(*9) The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
 