Product Information ---Option
Braking resistor DC REACTOR Devices requiring wiring
Interface card    
Devices requiring wiring
Type and specifications
Power
supply
voltage
Applicable
motor rating
(HP)
Inverter
type
MCCB, ELCB
rated current (A)
Magnetic contactor (MC) Recommended cable size (mm2) *1
Input circuit Output
circuit
Main power input
(L1/R, L2/S, L3/T)
Inverter
output
[U, V, W]
DC Reactor
[P1, P (+)]
DC Reactor
[P (+), DB
For
control
circuit
For connection
with Inverter
G]
With DCR Without
DCR
With DCR Without
DCR
With DCR Without
DCR
Three-
phase
230V
1/8 FRNF12
E1□-2U
5 5 SC-05 SC-05 SC-05 2.0 2.0 2.0 2.0 2.0 0.75
to
1.25
2.0
1/4 FRNF25
E1□-2U
2.0 2.0 2.0 2.0 2.0
1/2 FRNF50
E1□-2U
2.0 2.0 2.0 2.0 2.0
1 FRN001
E1□-2U
10 2.0 2.0 2.0 2.0 2.0
2 FRN002
E1□-2U
10 15 2.0 2.0 2.0 2.0 2.0
3 FRN003
E1□-2U
20 2.0 2.0 2.0 2.0 2.0
5 FRN005
E1□-2U
20 30 SC-4-0 2.0 2.0 2.0 2.0 2.0
7.5 FRN007
E1□-2U
30 50 SC-4-0 SC-5-1 SC-4-0 2.0 3.5 3.5 3.5 2.0 3.5
10 FRN010
E1□-2U
40 75 SC-5-1 SC-N1 SC-5-1 3.5 5.5 3.5 5.5 2.0 5.5
15 FRN015
E1□-2U
50 100 SC-N1 SC-N2S SC-N1 5.5 14.0 8.0 8.0 2.0
20 FRN020
E1□-2U
75 125 SC-N2 SC-N3 SC-N2 14.0 22.0 14.0 14.0 2.0 8.0
Three-
phase
460V
1/2 FRNF50
E1□-4U
5 5 SC-05 SC-05 SC-05 2.0 2.0 2.0 2.0 2.0 0.75
to
1.25
2.0
1 FRN001
E1□-4U
2.0 2.0 2.0 2.0 2.0
2 FRN002
E1□-4U
10 2.0 2.0 2.0 2.0 2.0
3 FRN003
E1□-4U
15 2.0 2.0 2.0 2.0 2.0
5 FRN005
E1□-4U
10 20 2.0 2.0 2.0 2.0 2.0
7.5 FRN007
E1□-4U
15 30 2.0 2.0 2.0 2.0 2.0
10 FRN010
E1□-4U
20 40 SC-4-0 2.0 2.0 2.0 2.0 2.0 3.5
15 FRN015
E1□-4U
30 50 SC-4-0 SC-N1 SC-4-0 2.0 3.5 2.0 3.5 2.0
20 FRN020
E1□-4U
40 60 SC-5-1 SC-5-1 3.5 5.5 3.5 5.5 2.0
Single-
phase
230V
1/8 FRNF12
E1□-7U
5 5 SC-05 SC-05 SC-05 2.0 2.0 2.0 2.0 2.0 0.75
to
1.25
2.0
1/4 FRNF25
E1□-7U
2.0 2.0 2.0 2.0 2.0
1/2 FRNF50
E1□-7U
10 2.0 2.0 2.0 2.0 2.0
1 FRN001
E1□-7U
10 15 2.0 2.0 2.0 2.0 2.0
2 FRN002
E1□-7U
15 20 2.0 2.0 2.0 2.0 2.0
3 FRN003
E1□-7U
20 30 SC-5-1 2.0 3.5 2.0 2.0 2.0
The code in □ represents followings; S: standard model, E: EMC filter built-in type
The code in ■ represents followings; A(Asia), K(Korea, Taiwan) , C(China), J(Japan)
Note1) An external power supply of 24V is needed to use a separately sold option card.
Note2) The inverter that can be used with the SY card includes special specifications. When ordering the SY card, please order together with the inverter in a set.
The frame and series of the MCCB and GFCI models vary according to the transformer capacity and so on of the equipment. Choose the optimum ones according to the catalog and technical data of the circuit breaker and others.
Choose the optimum rated sensitive current of the ELCB according to technical data, too. The rated currents of the MCCB and GFCI specified in this table indicate those of SAB/ and SAR/ models.
Description in the above table may vary for different ambient temperatures, power supply voltages or other conditions.
*1: Use crimp terminals equipped with insulation sheath or those equipped with an insulation tube or the like.
The cable to be used is 600V-insulated cable with an allowable temperature of 75°C(167°F). The ambient temperature is assumed to be 50°C(122°F).
 