Item Explanation & Remarks(*) Related
function
code
Protection
Overcurrent
(Short-circuit)
(Ground fault)
Protects and stops the inverter when the following overcurrent flows during acceleration, deceleration, or constant speed rotation:
- Overcurrent caused by overload
- Overcurrent caused by short-circuit in output circuit
- Overcurrent caused by ground fault
* Ground fault can be detected at starting.
 
Overvoltage Stops the inverter by detecting overvoltage in DC link circuit during braking.
* 230V series: 460V DC 400V series: 800V DC
 
Incoming surge Protects the inverter from surge voltage entering between main circuit power cable and earth cable.  
Undervoltage Stops the inverter by detecting voltage drop in DC link circuit.
* 230V series: 200V DC 460V series: 800V DC
Details of operation can be selected with the function code F14.
F14
Input phase loss Stops or protects the inverter against input phase loss.
* Non-operation is also selectable.
H98
Output phase loss Stops the inverter by detecting output phase loss at the start of or during operation.
* Non-operation is also selectable.
H98
Overheating (Heat sink) Stops the inverter by detecting inverter heat sink temperature.  
(Braking resistor) Stops the inverter and built-in braking transistor if "discharging capability" or "allowable loss" set for the braking resistor is exceeded more frequently than the set number of times. F50
F51
Overload Stops the inverter by detecting the output current and internal temp. To calculate the IGBT internal temp.  
Motor
protection
(Electronic thermal) Stops the inverter to protect the motor when the set output. Current is exceeded.
* Thermal time constant can be adjusted (0.5 to 75.0min).
F10 to F12
(PTC thermistor) A PTC thermistor input stops the inverter to protect the motor. H26, H27
(Overload early warning) Warning signal can be output based on the set level before the inverter trips.
* Related transistor output: OL
E34, E35
Retry function When the motor is tripped and stopped, this function automatically resets the tripping state and restarts operation. Activated when the motor is tripped with the following trip codes:
..........
* Waiting time before resetting and the number of retry times can be set.
H04
H05
Environment
Installation location Shall be free from corrosive gases, flammable gases, oil mist, dusts, and direct sunlight.
Indoor use only.
* Pollution degree 2 when the Low Voltage
Directives are used.
 
Ambient temperature -10 to +50°C(14 to 122°F)
* -10 to 40°C(14 to 122°F) when inverters are installed side by side without clearance.
 
Ambient humidity 5 to 95%RH (no condensation)  
Altitude
Altitude Output derating
3281 ft (1000 m) or lower None
3284 to 6562 ft (1001 to 2000 m) Decreases
6565 to 9843 ft (2001 to 3000 m) Decreases*
* If the altitude exceeds 6562 ft (2000 m), insulate the
interface circuit from the main power supply to
conform to the Low Voltage Directives.
 
Vibration 3mm (vibration width): 2 to less than 9Hz,
9.8m/s2: 9 to less than 20Hz
2m/s2: 20 to less than 55Hz
1m/s2: 55 to less than 200Hz
 
Storage Amb. temp. -25 to +70°C(-13 to 158°F)  
Amb. humidity 5 to 95%RH (no condensation)  
 