Fuji Electric Corp. of America

Product Information
Background,Concept,Terget
Appearance, Keypad
Major Functions, Features
Model Variation
Specifications
External Dimensions
Connection Diagram
Option
Application
Download
FAQ
Inquiries
Site Map
   
Item Explanation & Remarks(*) Related
function
code
Output frequency
Setting range Maximum frequency 25 to 400Hz F03
Base frequency 25 to 400Hz F04
Starting frequency 0.1 to 60.0Hz F23
Carrier frequency 0.75 to 15kHz
* Frequency may drop automatically to protect the inverter running at 7kHz or more.
This protective operation can be canceled by function code H98.
F26, F27,
H98
Accuracy(Stability)  Analog setting: ±2% of maixmum frequency (at 25±10°C(77±50°F))
Digital setting: ±0.01% of maixmum frequency (at -10 to +50°C(14 to 122°F))
 
Setting resolution
Analog setting: 1/1000 of maixmum frequency (ex. 0.06Hz at 60Hz, 0.4Hz at 400Hz)
Keypad setting: 0.01Hz (99.99Hz or less), 0.1Hz (100.0Hz or more)
Link setting: Selectable from 2 types
- 1/2000 of maixmum frequency
(ex. 0.003Hz at 60Hz, 0.02Hz at 400Hz)
- 0.01Hz (fixed)
* Includes the potentiometer on the keypad.
Setting with,keys.
 
Control
Control method V/f control (Simplified torque-vector control)  
Voltage/freq. characteristic
(Non-linear V/f setting)
- Possible to set output voltage at base frequency and at maixmum output frequency (common spec).
- AVR control can be turned ON or OFF (Factory setting: OFF).
* Three-phase 230V, single-phase 230V: 80 to 240V
Three-phase 460V: 160 to 500V
F03 to F05
1 point (Desired voltage and frequency can be set.) H50,H51
Torque boost
(Load selection)
Torque boost can be set with the function code F09.
* Set when 0, 1, 3, or 4 is selected at F37.
F09,F37
Select application load type with the function code F37.
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy-save operation (variable torque load in acceleration/deceleration)
4: Auto energy-save operation (constant torque load in acceleration/deceleration)
5: Auto energy-save operation (auto torque boost in acceleration/deceleration)
F09,F37
Starting torque 150% or over (Auto torque boost in 5Hz operation)  
Start/stop Keypad operation: Start (FWD/REV) and stop with,keys
* Remote keypad (option) is
also usable.
F02
External signal (digital input): FWD, REV, coast to stop command, etc.  
Link operation: Communication via RS485
* RS485 communication function is optional.
H30,
y01 to y10,
y99
 


Previous Top of Page Next