Single-phase series
 
Item Specifications
Input power source Single-phase 230V
Type(FRNC1E-7U) FRNF12 C1E-7U FRNF25 C1E-7U FRNF50 C1E-7U FRN001 C1E-7U FRN002 C1E-7U FRN003 C1E-7U
Nominal applied motor[HP](*1) 1/8 1/4 1/2 1 2 3
Output ratings Rated capacity[kVA](*2) 0.31 0.59 1.1 1.9 3.1 4.3
Rated voltage[V](*3) Three-phase, 200V/50Hz, 200, 220, 230V/60Hz
Rated current[A](*4) 0.8 (0.7) 1.5 (1.4) 3.0 (2.5) 5.0 (4.2) 8.0 (7.0) 11.0 (10.0)
Overload capability 150% of rated current for 1min, 200% of rated current for 0.5s
Rated frequency[Hz] 50, 60Hz
Input ratings Phases, voltage, frequency Single-phase, 200 to 240V, 50/60Hz
Voltage/frequency variations Voltage: +10 to -10%, Frequency: +5 to -5%
Momentary voltage dip capability(*5) When the input voltage is 165V or more, the inverter continues operation. If it drops below 165V, the inverter operates for 15ms.
Rated current [A](*6) (with DCR) 1.1 2.0 3.5 6.4 11.6 17.5
(without DCR) 1.8 3.3 5.4 9.7 16.4 24.8
Required power supply capacity[kVA](*7) 0.3 0.4 0.7 1.3 2.4 3.5
Braking Torque[%](*8) 150 100 50 30
Torque[%](*9) - 150
DC injection braking Starting frequency: 0.0 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
Enclosure (IEC60529) IP 20,UL open type (*11)
Cooling method Natural cooling Fan cooling
Weight / Mass[1bs.(kg)] 1.5(0.7) 1.5(0.7) 1.5(0.7) 2.6(1.2) 5.3(2.4) 6.4(2.9)
(*1) Standard 4-pole motor
(*2) Rated capacity is calculated by regarding the output rated voltage as 220V for three-phase 230V and single-phase 230V series, and as 440V for three-phase 460V series.
(*3) Output voltage cannot exceed the power supply voltage.
(*4) Use the inverter at the current given in ( ) or below when the carrier frequency setting is higher than 4kHz (F26 :4 to 15) or the ambient temperature is 40°C (104°F) or higher.
(*5) Tested under the standard load condition (85% load for nominal applied motor).
(*6) Calculated under Fuji-specified conditions.
(*7) Obtained when a DC REACTOR (option) is used.
(*8) Average braking torque obtained with AVR control OFF (Varies with the efficiency of the motor.)
(*9) Average braking torque obtained by use of external braking resistor (standard type available as option)
(*10) Voltage unbalance [%] = Max voltage [V] - Min voltage [V] /Three-phase average voltage [V] X67
(IEC 61800-3 (5.2.3))
If this value is 2 to 3%, use AC REACTOR (ACR).
(*11) NEMA1 kit (option) is required for the enclosure conforming to the UL standard TYPE1 (NEMA1).
Use the inverter in the ambient temperature range from -10 to +40°C (14 to 104°F).
(*12) When driven by 100 VAC, the single-phase 115 V class series of inverters limit their shaft output and maximum output torque as listed below. This is to prevent their output voltage from decreasing when load is applied.
 
  Shaft output (%) Maximum torque (%)
w/o DC reactor (DCR) 90 150
w/ DC reactor (DCR) 85 120