Standard specifications
 
Single-phase series
 
Item Specifications
Input power source Single-phase 230V Single-phase 115V *12)
Type(FRNC1S-7U) FRNF12
C1S-7U
FRNF25
C1S-7U
FRNF50
C1S-7U
FRN001
C1S-7U
FRN002
C1S-7U
FRN003
C1S-7U
FRNF12
C1S-6U
FRNF25
C1S-6U
FRNF50
C1S-6U
FRN001
C1S-6U
Nominal applied motor[HP](*1) 1/8 1/4 1/2 1 2 3 1/8 1/4 1/2 1
Output ratings Rated capacity[kVA](*2) 0.31 0.59 1.1 1.9 3.1 4.3 0.26 0.53 0.95 1.6
Rated voltage[V](*3) Three-phase, 200V/50Hz, 200V, 220V, 230V/60Hz
Rated current[A](*4) 0.8 (0.7) 1.5 (1.4) 3.0 (2.5) 5.0 (4.2) 8.0 (7.0) 11.0 (10.0) 0.7 1.4 2.5 4.2
Overload capability 150% of rated current for 1 min, 200% of rated current for 0.5s
Rated frequency[Hz] 50, 60Hz
Input ratings Phases, voltage, frequency Single-phase, 200 to 240V, 50/60Hz Single-phase, 100 to 120V, 50/60Hz
Voltage/frequency variations Voltage: +10 to -10% Frequency: +5 to -5%
Momentary voltage dip capability(*5) When the input voltage is 165V or more, the inverter continues operation. If it drops below 165V, the inverter operates for 15ms. When the input voltage is 85V or more, the inverter continues operation. If it drops below 85V, the inverter operates for 15ms.
Rated current [A](*6) (with DCR) 1.1 2.0 3.5 6.4 11.6 17.5 2.2 3.8 6.4 12.0
(without DCR) 1.8 3.3 5.4 9.7 16.4 24.8 3.6 5.9 9.5 16.1
Required power supply capacity[kVA](*7) 0.3 0.4 0.7 1.3 2.4 3.5 0.3 0.5 0.7 1.3
Braking Torque[%](*8) 150 100 50 30 150 100
Torque[%](*9) - 150 - 150
DC injection braking Starting frequency: 0.0 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
Enclosure (IEC60529) IP 20,UL open type (*11) IP20
Cooling method Natural cooling Fan cooling Natural cooling
Weight / Mass[1bs.(kg)] 1.3(0.6) 1.3(0.6) 1.3(0.6) 1.8(0.8) 3.7(1.7) 5.1(2.3) 1.3(0.6) 1.3(0.6) 1.5(0.7) 2.6(1.2)
(*1) Standard 4-pole motor
(*2) Rated capacity is calculated by regarding the output rated voltage as 220V for three-phase 230V and single-phase 230V series, and as 440V for three-phase 460V series.
(*3) Output voltage cannot exceed the power supply voltage.
(*4) Use the inverter at the current given in ( ) or below when the carrier frequency setting is higher than 4kHz (F26 :4 to 15) or the ambient temperature is 40°C (104°F) or higher.
(*5) Tested under the standard load condition (85% load for nominal applied motor).
(*6) Calculated under Fuji-specified conditions.
(*7) Obtained when a DC REACTOR (option) is used.
(*8) Average braking torque obtained with AVR control OFF (Varies with the efficiency of the motor.)
(*9) Average braking torque obtained by use of external braking resistor (standard type available as option)
(*10) Voltage unbalance [%] = Max voltage [V] - Min voltage [V] /Three-phase average voltage [V] X67
(IEC 61800-3 (5.2.3))
If this value is 2 to 3%, use AC REACTOR (ACR).
(*11) NEMA1 kit (option) is required for the enclosure conforming to the UL standard TYPE1 (NEMA1).
Use the inverter in the ambient temperature range from -10 to +40°C (14 to 104°F).
(*12) When driven by 100 VAC, the single-phase 115 V class series of inverters limit their shaft output and maximum output torque as listed below. This is to prevent their output voltage from decreasing when load is applied.
 
  Shaft output (%) Maximum torque (%)
w/o DC reactor (DCR) 90 150
w/ DC reactor (DCR) 85 120
How to read the model number