| Type FRN¤¤¤P11S-2UX | 007 | 010 | 015 | 020 | 025 | 030 | 040 | 050 | 060 | 075 | 100 | 125 | 150 | |||||
|
7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | 150 | |||||
| Output ratings |
|
8.8 | 12 | 17 | 22 | 27 | 31 | 46 | 58 | 72 | 86 | 113 | 138 | 165 | ||||
|
Three-phase 200V/50Hz 200, 220V, 230V/60Hz | |||||||||||||||||
|
22 | 29 | 42 | 55 | 67 | 78 | 115 | 145 | 180 | 215 | 283 | 346 | 415 | |||||
| Overload capability | 110% of rated current for 1min | |||||||||||||||||
|
50, 60Hz | |||||||||||||||||
| Input ratings |
Phases, Voltage, Frequency | Three-phase 200 to 230V 50/60Hz | Three-phase 200 to 220V/50Hz (220 to 230V/50Hz) *5) 200 to 230V/60Hz | |||||||||||||||
| Voltage / frequency variations | Voltage : +10 to –15% ( Voltage unbalance *6) : 2% or less ) Frequency :+5 to –5% | |||||||||||||||||
| Momentary voltage dip capability *7) | When the input voltage is 165V or more, the inverter can be operated continuously. When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . The smooth recovery method is selectable. |
|||||||||||||||||
| Rated current *8) A |
(with DCR) | 19.7 | 26.9 | 39.0 | 54.0 | 66.2 | 78.8 | 109 | 135 | 163 | 199 | 272 | 327 | 400 | ||||
| (without DCR) | 40.8 | 52.6 | 76.9 | 98.5 | 117 | 136 | 168 | 204 | 243 | 291 | - | - | - | |||||
|
6.9 | 9.4 | 14 | 19 | 23 | 28 | 38 | 47 | 57 | 69 | 95 | 114 | 139 | |||||
| Control | Starting torque | 50% | ||||||||||||||||
| Braking | Braking torque *10) | 20% | 10 to 15% | |||||||||||||||
|
No limit | |||||||||||||||||
|
No limit | |||||||||||||||||
| Braking torque (Using options) | 100% | 70% | ||||||||||||||||
| DC injection braking | Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 80% of rated current | |||||||||||||||||
| Enclosure (IEC 60529) | IP 40 ( NEMA1 ) | IP 00 ( NEMA1 : Option ) | ||||||||||||||||
| Cooling method | Fan cooling | |||||||||||||||||
| Standards | -UL/cUL -Low Voltage Directive -EMC Directive TÜV (up to 22kW) -IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems) -IEC 61800-3 (EMC product standard including specific test methods) |
|||||||||||||||||
|
12.6 (5.7) |
12.6 (5.7) |
12.6 (5.7) |
22 (10) |
22 (10) |
23.1 (10.5) |
63.9 (29) |
63.9 (29) |
79.4 (36) |
97 (44) |
101.4 (46) |
154.3 (70) |
253.5 (115) |
|||||
NOTES:
*1) Inverter output capacity (kVA) at 460V in 460V , 230V in 230V. *2) Output voltage is proportional to the power supply voltage and cannot exceed the
power supply voltage. *3) Current derating may be required in case of low impedance loads such as high frequency motor. *4) When the input voltage is 380V/50Hz or
380 to 415V/60Hz, the tap of the auxiliary transformer must be changed. *5) Order individually. *6) Refer to the IEC 61800-3( 5.2.3 ). *7) Tested at standard load
condition (85% load). *8) This value is under FUJI original calculation method. (Refer to the Technical Information.) *9) When power-factor correcting DC reactor (DCR)
is used. *10) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)