Product Information - Specifications

Standard specifications Three-phase 208V Three-phase 460V
Common specifications

Standard specifications
  Three-phase 460V
- 1 to 75HP
 
Item Specifications
Type
(FRN _ _ _ F1S-4U)
001 002 003 005 007 010 015 020 025 030 040 050 060 075
Nominal applied motor [HP] *1 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
Output ratings Rated capacity [kVA] *2 1.9 2.9 4.3 7.1 9.9 13 18 23 29 35 47 57 67 83
Rated voltage [V] *3 Three-phase, 380 to 480V (With AVR function)
Rated current [A] *4 2.5 3.7 5.5 9.0 12.5 16.5 23 30 37 44 59 72 85 105
Overload capability 120% of rated current for 1min.
Rated frequency 50, 60 Hz
Input ratings Phases,
voltage,
frequency
Main power supply Three-phase, 380 to 480V, 50/60Hz Three-phase, 380 to 440V,50Hz
Three-phase, 380 to 480V,60Hz
Auxiliary control
power input
Single-phase, 380 to 480V, 50/60Hz
Auxiliary fan
power input *5
None Single-phase,
380 to 440V/50Hz,
Single-phase,
380 to 480V/60Hz
Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance 2% or less) *9, Frequency: +5 to -5%
Rated current [A] *6(with DCR) 1.3 2.5 3.8 6.2 8.9 11.8 17.7 23.7 29.6 35.5 46.8 57.0 68.4 85.7
(without DCR) 2.5 4.8 6.9 10.8 14.5 19.1 27.7 36.0 43.6 50.9 64.0 78.5 93.7 118
Required power supply capacity [kVA] *7 1.1 2.0 3.1 5.0 7.1 10 15 19 24 29 38 46 55 69
Braking Torque [%] *8
20
10 to 15
DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time:0.0 to 30.0s, Braking level: 0 to 60%
DC reactor (DCR) Option
Applicable safety standards UL508C, C22.2 No.14, EN50178-1997
Enclosure (IEC60529) IP20, UL open type IP00, UL open type
Cooling method Natural cooling Fan cooling
Mass [lbs(kg)] 6.8
(3.1)
7.1
(3.2)
7.3
(3.3)
7.5
(3.4)
7.5
(3.4)
13
(6.0)
13
(6.0)
15
(6.9)
22
(9.9)
22
(9.9)
25
(11.5)
51
(23)
53
(24)
73
(33)
TOP
 
  - 100 to 900HP
 
Item Specifications
Type
(FRN _ _ _ F1S-4U)
100 125 150 200 250 300 350 400 450 500 600 700 800 900
Nominal applied motor [HP] *1 100 125 150 200 250 300 350 400 450 500 600 700 800 900
Output ratings
Rated capacity [kVA] *2 110 133 161 191 240 286 330 380 414 517 589 669 764 828
Rated voltage [V] *3 Three-phase, 380 to 480V (With AVR function)
Rated current [A] *4 139 168 203 240 302 360 415 477 520 650 740 840 960 1040
Overload capability 120% of rated current for 1min.
Rated frequency 50, 60 Hz
Input ratings
Phases,
voltage,
frequency
Main power supply Three-phase, 380 to 440V, 50Hz
Three-phase, 380 to 480V, 60Hz
Auxiliary control
power input
Single-phase, 380 to 480V, 50/60Hz
Auxiliary fan
power input *5
Single-phase, 380 to 440V/50Hz
Single-phase, 380 to 480V/60Hz
Voltage/frequency variations Voltage: +10 to -15% (Voltage unbalance 2% or less) *9, Frequency: +5% to -5%
Rated current [A] *6(with DCR) 113 140 169 222 275 330 382 440 495 545 652 756 869 981
(without DCR) - - - - - - - - - - - - - -
Required power supply capacity [kVA] *7 91 112 135 177 220 263 305 351 395 435 520 603 693 782
Braking
Torque [%] *8
10 to 15
DC injection braking Starting frequency: 0.0 to 60.0Hz, Braking time:0.0 to 30.0s, Braking level: 0 to 60%
DC reactor (DCR) Standard
Applicable safety standards UL508C, C22.2 No.14,
EN50178-1997
UL508C, C22.2 No.14
Enclosure (IEC60529) IP00, UL open type
Cooling method Fan cooling
Mass [lbs(kg)] 75
(34)
93
(42)
99
(45)
139
(63)
212
(96)
212
(96)
216
(98)
357
(162)
357
(162)
529
(240)
529
(240)
783
(355)
794
(360)
794
(360)

*1Standard 4-pole motor
*2 Rated capacity is calculated by assuming the output rated voltage as 460V for three-phase 460V.
*3 Output voltage cannot exceed the power supply voltage.
*4 An excessively low setting of the carrier frequency may result in the higher motor temperature or tripping of the inverter by its overcurrent limiter setting. Lower the continuous load or maximum load instead. (When setting the carrier frequency (F26) to 1kHz, reduce the load to 80% of its rating.)
*5 Use [R1,T1] terminals for driving AC cooling fans of an inverter powered by the DC link bus, such as by a high power factor PWM converter. (In ordinary operation, the terminals are not used.)
*6 Calculated under Fuji-specified conditions.
*7 Obtained when a DC reactor (DCR) is used.
*8 Average braking torque (Varies with the efficiency of the motor.)
*9 Voltage unbalance (%) = Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) x 67 (IEC61800-3(5.2.3))
If this value is 2 to 3%, use an AC reactor (ACR).