Appearance
Major Functions, Features
Model Variations
Energy Savings with Inverter
Specifications
External Dimensions
Wiring Diagram
Connection with Peripherals
Options
Power
supply
voltage
Inverter type
Required torque Ib-in (N-m)
Wire size AWG
Class
J
fuse
size
(A)
Circuit
breaker
trip
size
(A)
Main terminal
Aux.
Control
Power
Supply
R0, T0
Control
circuit
Main terminal
Aux.
Control
Power
Supply
R0, T0
Aux. Fan
Power
Supply
R1, T1
Control
circuit
Europe
type
terminal
block
Europe
type
terminal
block
Three-phase
208V
FRN001F1S-2U
15.9
(1.8)
10.6
(1.2)
4.4
(0.5)
14
14
-
20
10
15
FRN002F1S-2U
15
FRN003F1S-2U
20
20
FRN005F1S-2U
12
35
30
FRN007F1S-2U
33.6
(3.8)
8
60
50
FRN010F1S-2U
4
70
70
FRN015F1S-2U
51.3
(5.8)
100
100
FRN020F1S-2U
3
125
125
FRN025F1S-2U
2
150
150
FRN030F1S-2U
119.4
(13.5)
1/0
175
175
FRN040F1S-2U
200
200
FRN050F1S-2U
238.9
(27)
3/0
14
225
225
FRN060F1S-2U
4/0
300
300
FRN075F1S-2U
300
FRN100F1S-2U
2/0x2
350
350
FRN125F1S-2U
424.7
(48)
4/0x2
400
400
Three-phase
460V
FRN001F1S-4U
15.9
(1.8)
10.6
(1.2)
4.4
(0.5)
14
14
-
20
6
15
FRN002F1S-4U
10
FRN003F1S-4U
15
FRN005F1S-4U
20
20
FRN007F1S-4U
30
30
FRN010F1S-4U
33.6
(3.8)
12
40
FRN015F1S-4U
10
50
40
FRN020F1S-4U
51.3
(5.8)
8
70
50
FRN025F1S-4U
80
70
FRN030F1S-4U
6
100
80
FRN040F1S-4U
119.4
(13.5)
4
100
FRN050F1S-4U
2
125
125
FRN060F1S-4U
1
150
150
FRN075F1S-4U
1/0
14
175
175
FRN100F1S-4U
3x2
FRN125F1S-4U
238.9
(27)
4/0
200
200
FRN150F1S-4U
250
225
225
FRN200F1S-4U
2/0x2
300
300
FRN250F1S-4U
424.7
(48)
500
400
400
FRN300F1S-4U
4/0x2
450
450
FRN350F1S-4U
300x2
500
500
FRN400F1S-4U
350x2
600
600
FRN450F1S-4U
400x2
700
700
FRN500F1S-4U
300x3
FRN600F1S-4U
350x3
1000
1000
FRN700F1S-4U
300x4
FRN800F1S-4U
350x4
1200
1200
FRN900F1S-4U
400x4
1600
1600
*1 :
Select the rated current of a fuse or a circuit breaker which is suitable to the connecting wire size.